Siemens SINAMICS G120 Operating Instructions Manual page 200

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Advanced commissioning
6.3 Adapt the default setting of the terminal strip
Advanced settings
You can debounce the digital input signal using parameter p0724.
For more information, please see the parameter list and the function block diagrams 2220 f of
the List Manual.
Analog inputs as digital inputs
NOTICE
Overcurrent at an analog input
If the analog input switch is set to "Current input" (I), a 10V or 24V voltage source results in
an overcurrent at the analog input. An overcurrent condition destroys the analog input.
● If you use an analog input as a digital input, then you must set the analog input switch to
200
Overview of the manuals (Page 537)
"Voltage" (U).
To use an analog input as additional digital input,
you must interconnect the corresponding status pa‐
rameter r0722.11 or r0722.12 with a binector input
of your choice.
You may operate the analog input as digital input
with 10 V or with 24 V.
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120p

Table of Contents