Siemens SINAMICS G120 Operating Instructions Manual page 409

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Number
Cause
F07086
Switching over units: Parameter lim‐
F07088
it violation
F07320
Automatic restart aborted
A07321
Automatic restart active
F07330
Search current measured too low
A07353
DC quantity control deactivated
F07390
Forming the DC link capacitors was
faulty
A07391
Forming the DC link capacitors ac‐
tive
A07400
DC-link voltage maximum controller
active
A07409
V/f control, current limiting control‐
ler active
F07426
Technology controller actual value
limited
A07444
PID autotuning is activated
F07445
PID autotuning canceled
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Remedy
Check the adapted parameter values and if required correct.
Increase the number of restart attempts (p1211). The current number of
start attempts is shown in r1214.
Increase the wait time in p1212 and/or monitoring time in p1213.
Connect an ON command (p0840).
Increase the monitoring time of the power unit or switch off (p0857).
Reduce the wait time for resetting the fault counter p1213[1] so that fewer
faults are registered in the time interval.
Explanation: The automatic restart (AR) is active. During voltage recovery
and/or when remedying the causes of pending faults, the drive is automat‐
ically switched back on.
Increase the search current (p1202), check the motor connection.
The controller to suppress DC components in the motor current was at its
limit and deactivated itself.
● Increase the integral time p3858 of the DC quantity controller
● Decrease the gain p3857 of the DC quantity controller
The inverter has canceled the "Forming the DC link capacitors" function
(r3382.3 = 1). The expected DC link voltage is outside the tolerance.
● Check the inverter, e.g. supply voltage and connecting terminals
● Set the forming duration again (p3380 > 0), and restart forming.
The "DC link forming" function is active. After forming has been completed,
the inverter withdraws the alarm (r3382.2 = 1).
If the controller is not to intervene:
● Increase the ramp-down times.
● Deactivate the Vdc_max control (p1240 = 0 for vector control, p1280 =
0 for U/f control).
The alarm automatically disappears after one of the following measures:
● Increase the current limit (p0640).
● Reduce the load.
● Increase the ramp-up time to the speed setpoint.
● Adapt the limits to the signal level (p2267, p2268).
● Check the actual value scaling (p2264).
Automatic setting of the PID controller (autotuning) is active (p2350 > 0).
The alarm disappears automatically after completion of the autotuning.
The inverter has canceled the automatic setting of the PID controller (au‐
totuning) because of a fault.
Remedy: Increase p2355 and restart autotuning.
Alarms, faults and system messages
8.6 List of alarms and faults
409