Stall protection

In applications with extruders or mixers, the motor can block for an excessive mechanical load.
For a blocked motor, the motor current corresponds to the set current limit without the speed
reaching the specified setpoint.
If the speed lies below the speed threshold p2175 for the time p2177 while the motor current
reaches the current limit, the inverter signals "Motor blocked" and fault F07900.
Parameter
r0063
p2175
p2177
r2198
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Description
Actual speed value [rpm]
[0] = Unsmoothed
[1] = Smoothed with p0045
Motor blocked speed threshold (factory setting: 120 rpm)
p2175 = 0: Blocking protection deactivated
Motor blocked delay time (factory setting: 3 s)
Status word monitoring 2
r2198.06 = 1: Motor blocked
Advanced commissioning