Siemens SINAMICS G120 Operating Instructions Manual page 209

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Application example: Defining the function of an analog output
Advanced settings
You can manipulate the signal that you output via an analog output, as follows:
● Absolute-value generation of the signal (p0775)
● Signal inversion (p0782)
Additional information is provided in the parameter list of the List Manual.
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Overview of the manuals (Page 537)
6.3 Adapt the default setting of the terminal strip
To output the inverter output current via analog output 0, you
must interconnect AO 0 with the signal for the output current.
Set p0771 = 27.
Advanced commissioning
209