Siemens SINAMICS G120 Operating Instructions Manual page 354

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Advanced commissioning
6.36 Bypass
Changeover depending on the speed
Figure 6-64
If the speed setpoint r1119 lies above the bypass speed threshold p1265, the inverter switches
the motor to line operation.
If the speed setpoint falls below the bypass speed threshold, the inverter switches the motor
to inverter operation.
Interaction with other functions
● Flying restart
The "Flying restart" function must be activated for the "Bypass" function (p1200 = 1 or 4).
● Emergency operation
The activated "Essential service mode" function influences the "Bypass" function.
● Inverter control
For operation of the motor on the line supply, the inverter no longer responds to the OFF1
command, but rather only to OFF2 and OFF3.
354
Changeover depending on the speed (p1267.1 = 1)
Flying restart – switching on while the motor is running (Page 340)
Essential service mode (Page 245)
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120p

Table of Contents