Advanced commissioning
6.24 Motor control
Table 6-47
Linear and parabolic characteristics
Requirement
Application examples
The required tor‐
Eccentric-worm pump,
que is independ‐
compressor
ent of the speed
The required tor‐
Centrifugal pumps, radi‐
que increases with
al fans, axial fans, com‐
the speed
pressors
Table 6-48
Characteristics for special applications
Requirement
Application examples
Applications with a
Centrifugal pumps, radi‐
low dynamic re‐
al fans, axial fans
sponse and con‐
stant speed
Additional information on V/f characteristics can be found in the parameter list and in the
function diagrams 6300 ff of the List Manual.
Characteristics after selecting the application class Standard Drive Control
Selecting application class Standard Drive Control reduces the number of characteristics and
the setting options:
● A linear and a parabolic characteristic are available.
● Selecting a technological application defines the characteristic.
● The following cannot be set - ECO mode, FCC, the programmable characteristic and a
specific voltage setpoint.
300
Remark
-
The inverter equalizes the voltage drops
across the stator resistance. Recommen‐
ded for motors less than 7.5 kW.
Precondition: You have set the motor data
according to the rating plate and have per‐
formed the motor identification after the ba‐
sic commissioning.
Lower losses in the motor and inverter than
for a linear characteristic.
Remark
The ECO mode results in additional energy
saving when compared to the parabolic
characteristic.
If the speed setpoint is reached and re‐
mains unchanged for 5 seconds, the inver‐
ter again reduces its output voltage.
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Characteristic
Parameter
Linear
p1300 = 0
Linear with Flux
p1300 = 1
Current Control
(FCC)
Parabolic
p1300 = 2
Characteristic
Parameter
ECO mode
p1300 = 4
(linear char‐
acteristic
ECO)
or
p1300 = 7
(parabolic
characteris‐
tic ECO)