5.6

Restoring the factory setting

There are cases where something goes wrong when commissioning a drive system e.g.:
● The line voltage was interrupted during commissioning and you were not able to complete
commissioning.
● You got confused during the commissioning and you can no longer understand the
individual settings that you made.
● You do not know whether the inverter was already operational.
In cases such as these, reset the inverter to the factory settings.
Restore the factory inverter settings
Procedure with STARTER
Proceed as follows to reset the inverter to factory settings:
1. Select your drive.
2. Go online.
3. Open "Drive Navigator".
4. Select the "Commissioning" button.
5. Press the "Factory setting" button.
6. ☑ In the screen form, select "After loading copy RAM to ROM".
7. Start the reset.
8. Wait until the inverter has been reset to the factory setting.
You have reset the inverter to factory settings.
Procedure with Startdrive
Proceed as follows to reset the inverter to factory settings:
1. Go online.
2. Select "Commissioning".
3. Select "Backing up/reset".
4. Select "All parameters are reset".
Converter with the CU230P-2 Control Units