Installing
4.3 Installing Power Modules
4.3.3
Dimension drawings, drilling dimensions for the PM230 Power Module, IP20
The following dimension drawings and drilling patterns are not to scale.
Frame sizes FSA ... FSC
Table 4-5
Frame
size
FSA
FSB
FSC
BOP-2, IOP-2 or blanking cover
1)
Power Module depth without Control Unit: 165 mm
2)
Table 4-6
Frame size
FSA
FSB
FSC
You can mount the Power Modules without any lateral cooling air clearance. For tolerance reasons,
1)
we recommend a lateral clearance of approx. 1 mm.
68
Dimensions depend on the operator panel (OP) that is inserted
Width
Height [mm]
[mm]
without shield
plate
73
196
100
292
140
355
Drilling dimensions, cooling clearances and fixing
Drilling dimensions [mm] Cooling air clearances [mm]
b
h
62.3
186
80
281
120
343
Mounting depth in the cabinet with
with shield plate
without OP
276
370
432
c
Top
Bottom
6
80
100
6
80
100
6
80
100
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Control Unit (CU) [mm]
2)
with OP
224
235
224
235
224
235
Fixing/torque
1)
[Nm]
Front
---
2 x M4 / 2.5
---
4 x M4 / 2.5
---
4 x M5 / 3.0
1)