Adapting the characteristic
You must define your own characteristic if none of the default types match your particular
application.
Application example
The inverter should convert a 6 mA ... 12 mA signal into the value range ‑100 % ... 100 % via
analog input 0. The wire break monitoring of the inverter should respond when 6 mA is fallen
below.
Requirement
You have set analog input 0 as a current input ("I") via the DIP switch on the
Control Unit.
Procedure
Defining the function of an analog input
You define the analog input function by interconnecting a connector input of your choice with
parameter p0755. Parameter p0755 is assigned to the particular analog input based on its
index, e.g. parameter p0755[0] is assigned to analog input 0.
Table 6-6
CI
p1070 Main setpoint
p1075 Supplementary setpoint
A complete list of the connector inputs is provided in the List Manual.
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Frequently used connector inputs (CI) of the inverter
Significance
Overview of the manuals (Page 537)
6.3 Adapt the default setting of the terminal strip
Set the following parameters to set the analog input as cur‐
rent input with monitoring:
1. set p0756[0] = 3
You have defined analog input 0 as current input with wire
break monitoring.
2. Set p0757[0] = 6.0 (x1)
3. Set p0758[0] = -100.0 (y1)
4. Set p0759[0] = 12.0 (x2)
5. Set p0760[0] = 100.0 (y2)
6. Set p0761[0] = 6
An input current < 6 mA results in fault F03505.
CI
Significance
p2253 Technology controller setpoint 1
p2264 Technology controller actual value
Advanced commissioning
205