Normal PID Feedback
Input the PID feedback signal from one of the sources listed in
PID Feedback Source
Analog Input A1
Analog Input A2
Analog Input A3
Pulse Input RP
Note:
A duplicate allocation of the PID feedback input will cause an oPE07 (Multi-Function Analog Input Selection Error) alarm.
Differential Feedback
The second PID feedback signal for differential feedback can come from the sources listed in
feedback function is automatically enabled when a differential feedback input is assigned.
PID Differential Feedback Source
Analog Input A1
Analog Input A2
Analog Input A3
Note:
A duplicate allocation of the PID differential feedback input will cause an oPE07 (Multi-Function Analog Input Selection Error) alarm.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Table
Table 1.20 PID Feedback Sources
Table 1.21 PID Differential Feedback Sources
Set H3-02 = 16 (Differential PID Feedback)
Set H3-10 = 16 (Differential PID Feedback)
Set H3-06 = 16 (Differential PID Feedback)
1.20:
Settings
Set H3-02 = B
Set H3-10 = B
Set H3-06 = B
Set H6-01 = 1
Table
Settings
1.2 b: Application
1.21. The differential
35
1