No.
(Addr.
Name
Hex)
L8-19
Frequency Reduction Rate
(4BF)
during Overheat Pre-Alarm
Main Contactor and Cooling
L8-32
Fan Power Supply Failure
(4E2)
Selection
L8-38
Carrier Frequency
(4EF)
Reduction
L8-40
Carrier Frequency
(4F1)
Reduction Off Delay Time
L8-41
High Current Alarm
(4F2)
Selection
L8-78
Module Output Loss
(2CC)
Detection (LF3)
L8-86
Detection selection when
(2F3)
panel fan fails
L8-87
Detection selection when
(2F4)
diode converter(s) fan(s) fail
<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<4> Default setting is dependent on parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<5> Default setting is dependent on parameter A1-02, Control Method Selection.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Description
All Modes
Specifies the frequency reference reduction gain at overheat pre-alarm when
L8-03 = 4.
All Modes
Determines drive response when a fault occurs with the internal cooling fan.
0: Ramp to stop
1: Coast to stop
2: Fast stop (Decelerate to stop using the deceleration time set to C1-09)
3: Alarm only ("FAn" will flash)
4: Continue operation at reduced speed as set to L8-19.
V/f
V/f
V/f
V/f
V/f w PG
V/f w PG
V/f w PG
V/f w PG
OLV
OLV
OLV
OLV
OLV/PM
OLV/PM
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
CLV/PM
CLV/PM
0: Disabled
1: Enabled below 6 Hz
2: Enabled for the entire speed range
V/f
V/f
V/f
V/f
V/f w PG
V/f w PG
V/f w PG
V/f w PG
OLV
OLV
OLV
OLV
OLV/PM
OLV/PM
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
CLV/PM
CLV/PM
Sets the time that the drive continues running with reduced carrier frequency
after the carrier reduction condition is gone. Setting 0.00 s disables the carrier
frequency reduction time.
All Modes
0: Disabled
1: Enabled. An alarm is triggered at output currents above 150% of drive rated
current.
All Modes
Detects the loss of an output phase in any of the inverter output modules.
0: Disabled
1: Enabled
All Modes
Detects the loss of the drive panel fan by the panel fan input.
0: Ramp Stop (Fault)
1: Coast Stop (Fault)
2: Fast Stop (Fault)
3: Continue Running (Alarm)
4: As for continue Running at L8–19 Speed
5: Disabled
Note:
Settings 3 and 4 reduce inverter O/L level from 100% to 80 %.
All Modes
Detects the loss of the diode converter fan(s) by the fan control input.
0: Ramp Stop (Fault)
1: Coast Stop (Fault)
2: Fast Stop (Fault)
3: Continue Running (Alarm)
4: As for continue Running at L8–19 Speed
5: Disabled
Note:
Settings 3 and 4 reduce inverter O/L level from 100% to 80 %.
A.10 L: Protection Function
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
Values
Page
Default: 0.8
Min.: 0.1
153
Max.: 0.9
Default: 1
155
Range: 0 to 4
<4>
Default:
156
Range: 0 to 2
<5>
Default:
156
Min.: 0.00 s
Max.: 2.00 s
Default: 0
156
Range: 0, 1
Default: 1
157
Range: 0, 1
Default: 1
157
Range: 0, 5
Default: 1
157
Range: 0, 5
289
A