The fault restart function allows the drive to automatically clear a fault. The terminal set to 1E will close after the fault is
cleared and the drive has attempted to restart. If the drive cannot successfully restart within the number of attempts permitted
by L5-01, a fault will be triggered and the terminal set to 1E will open.
automatic restart.
Setting 1F: Motor Overload Alarm (oL1)
The output closes when the motor overload level estimated by the oL1 fault detection exceeds 90% of the oL1 detection level.
Refer to L1-01: Motor Overload Protection Selection on page
Setting 20: Drive Overheat Pre-Alarm (oH)
The output closes when the drive heatsink temperature reaches the level specified by parameter L8-02.
Overheat Alarm Level on page 152
Setting 22: Mechanical Weakening Detection
The output closes when a mechanical weakening situation is detected.
150
for details.
Setting 2F: Maintenance Period
The output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as determined
by the estimated performance life span of those components. Components performance life is displayed as a percentage on
the digital operator screen.
Setting 30: During Torque Limit
Note:
PM motor control modes are not available in A1000 HHP drive models.
The output closes when the motor is operating at the torque limit specified by the L7-oo parameters or an analog input. This
setting can only be used in OLV, CLV, AOLV/PM and CLV/PM control modes.
page 151
for details.
Setting 31: During Speed Limit
Note:
PM motor control modes are not available in A1000 HHP drive models.
The output closes when the speed limit has been reached. This function can be used in CLV and CLV/PM control modes.
Status
Open
The conditions described below are not present.
1. The frequency reference has reached the upper limit set in d2-01.
2. The frequency reference has fallen to the lower limit set in d2-02 or d2-03.
Closed
3. Parameter b1-05 is set to 1, 2, or 3, and the frequency reference has fallen below the minimum output frequency
(E1-09).
Setting 32: During Speed Limit in Torque Control
The motor torque and load torque are not in balance, causing the motor to accelerate. The output closes when the motor reaches
the speed limit.
Refer to d5: Torque Control on page 67
Setting 33: Zero Servo Complete
The output closes when Zero Servo is enabled and the load is locked into position within the allowable deviation (b9-02).
Refer to b9: Zero Servo on page 44
Setting 37: During Frequency Output
The output closes when the drive is outputting a frequency.
Status
Open
Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.
Closed
Drive is outputting frequency.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
for details on drive overheat detection.
and
Indicating Operation at the Speed Limit
for information on Zero Servo operation.
Refer to L5: Fault Restart on page 146
128.
Refer to Mechanical Weakening Detection on page
Refer to L7-01 to L7-04: Torque Limits on
Description
Description
1.7 H: Terminal Functions
for details on
Refer to L8-02:
on page
70
for details.
1
113

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents