2.2 Motor Performance Fine-Tuning
Name
(Parameter No.)
Stall Prevention
(L3-01 through L3-06, L3-11)
Torque Limits
(L7-01 through L7-04, L7-06, L7-07)
178
• Prevents motor speed loss and overvoltage when the load is too heavy or during sudden acceleration/
deceleration.
• Adjustment is not normally necessary because Stall Prevention is enabled as a default. Set L3-04 to 0 to
disable Stall Prevention during deceleration when using a braking resistor.
• Sets the maximum torque for OLV Control.
• Ensure that the drive capacity is greater than the motor capacity when increasing this setting. Motor speed
loss may occur with heavy loads.