Frequency reference
L4-03
Output frequency
User Set
Speed Agree 2
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 145
Setting 15: Frequency Detection 3
The output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-03 plus
the detection with set in L4-04. The terminal remains open until the output frequency or motor speed falls below the level set
in L4-03. The detection level L4-03 is a signed value; detection works in the specified direction only.
Status
Open
Output frequency or motor speed exceeded L4-03 plus L4-04.
Closed
Output frequency or motor speed is below L4-03 or has not exceeded L4-03 plus L4-04.
Frequency
detection 3
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 145
Setting 16: Frequency Detection 4
The output closes when the output frequency or motor speed (CLV, CLV/PM) is above the detection level set in L4-03. The
terminal remains closed until the output frequency or motor speed falls below L4-03 minus the setting of L4-04.
Status
Open
Output frequency or motor speed is below L4-03 minus L4-04 or has not exceeded L4-03.
Closed
Output frequency or motor speed exceeded L4-03.
Note:
The detection level L4-03 is a signed value; detection works in the specified direction only.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
0 Hz
OFF
ON
Figure 1.69 User-Set Speed Agree 2 Example with a Positive L3-04 Value
Output Frequency
ON
OFF
Figure 1.70 Frequency Detection 3 Example with a Positive L3-04 Value
Frequency reference
L4-03
+
L4-04
Frequency reference – L4-04
L4-03 – L4-04
During
Forward
OFF
ON
Description
L4-04
L4-03
Description
1.7 H: Terminal Functions
+
L4-04
Output frequency
Frequency
reference
for more details.