YASKAWA A1000 HHP Programming Manual page 200

High performance vector control drive
Table of Contents

Advertisement

2.4 Fault Detection
Digital Operator Display
Cause
Parameter settings are not appropriate for the
load
There is a fault on the machine side
Digital Operator Display
Cause
Parameter settings are not appropriate for the
load
There is a fault on the machine side
Digital Operator Display
Cause
Undertorque was detected and matched the
conditions for mechanical loss detection set to
L6-08
Digital Operator Display
<1>
Cause
The internal current sensor has detected a
current unbalance situation.
<1> Detected in models 4A0930 and 4A1200.
Digital Operator Display
Cause
Input power phase loss
One of the drive input power wiring terminals
is loose
There is a problem with the voltage from the
drive input power
The power has been interrupted
The main circuit capacitors are worn
200
Undertorque Detection 1
UL3
The current has fallen below the minimum value set for Torque Detection Level 1 (L6-02) for longer than
the allowable time (L6-03).
Check the settings of parameters L6-02 and L6-03.
Check the load for any problems.
Undertorque Detection 2
UL4
The current has fallen below the minimum value set for Torque Detection Level 2 (L6-05) for longer than
the allowable time (L6-06).
Check L6-05 and L6-06 settings
Check the load for any problems.
Mechanical Weakening Detection 2
UL5
The operation conditions matched the conditions set to L6-08.
Check the load side for any problems.
Current Unbalance
UnbC
Current flow has become unbalanced.
• Check wiring
• Check for damaged transistors.
• Check for short circuits or grounding problems on the connected motor.
DC Bus Undervoltage
Voltage in the DC bus fell below the undervoltage detection level (L2-05).
• For 400 V class drives: approximately 380 V (350 V when E1-01 is less than 400)
Uv1
• For 575 V class drives: approximately 475 V
• For 690 V class drives: approximately 570 V
The fault is output only if L2-01 is set to 0 or 1 and the DC bus voltage has fallen below the level set to
L2-05 for longer than the time set to L2-02.
• The main circuit drive input power is wired incorrectly.
• Correct the wiring.
• Ensure there are no loose terminals.
• Check for loose terminals.
• Check the voltage.
• Correct the voltage to be within the range listed in drive input power specifications.
• If there is no problem with the power supply to the main circuit, check for problems with the main
circuit magnetic contactor.
Correct the drive input power.
• Check the maintenance time for the capacitors (U4-05).
• Replace either the control board or the entire drive if U4-05 exceeds 90%. For instructions on replacing
the control board, contact Yaskawa or a Yaskawa representative.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents