Setting
Specification
0
50 Hz
1
60 Hz
2
60 Hz (with 50 Hz base)
3
72 Hz (with 60 Hz base)
4
50 Hz, Heavy Duty 2
5
50 Hz, Heavy Duty 1
6
50 Hz, Heavy Duty 1
7
50 Hz, Heavy Duty 2
8
50 Hz, mid starting torque
9
50 Hz, high starting torque
A
60 Hz, mid starting torque
B
60 Hz, high starting torque
C
90 Hz (with 60 Hz base)
D
120 Hz (with 60 Hz base)
E
150 Hz (with 60 Hz base)
F
60 Hz
<1>
<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04
to E1-13 are the same as those of setting 1.
The following tables show details on predefined V/f patterns.
Predefined V/f Patterns for all HHP models:
• 400 V Class 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty,
• 575 V Class 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty,
• 690 V Class 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty.
The values in the following graphs are specific to 400 V class drives. Multiply the values by 1.4375 for 575 V class drives.
Multiply the values by 1.725 for 690 V class drives.
Setting = 0
50 Hz
400
24
12
0
1.3 2.5
50
Frequency (Hz)
Setting = 4
50 Hz
400
70
10
0
1.3
25
50
Frequency (Hz)
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Table 1.31 Predefined V/f Patterns
Characteristic
Constant torque
Variable torque
High starting torque
Constant output
Constant torque
Table 1.32 Rated Torque Characteristics, Settings 0 to 3
Setting = 1
60 Hz
400
24
12
0
1.5 3
60
Frequency (Hz)
Table 1.33 Derated Torque Characteristics, Settings 4 to 7
Setting = 5
50 Hz
400
100
12
0
1.3
25
50
Frequency (Hz)
For general purpose applications. Torque remains constant
regardless of changes to speed.
For fans, pumps, and other applications where the required
torque changes as a function of the speed.
Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.
Output voltage is constant when operating at greater than
60 Hz.
For general purpose applications. Torque remains constant
regardless of changes to speed.
Setting = 2
60 Hz
400
24
12
0
1.5 3
50
60
Frequency (Hz)
Setting = 6
60 Hz
400
70
10
0
1.5
30
60
Frequency (Hz)
1.5 E: Motor Parameters
Application
Setting = 3
72 Hz
400
24
12
0
1.5 3
60
72
Frequency (Hz)
Setting = 7
60 Hz
400
100
12
0
1.5
30
60
Frequency (Hz)
1
75