YASKAWA A1000 HHP Programming Manual page 157

High performance vector control drive
Table of Contents

Advertisement

n
L8-78: Power Unit Output Phase Loss Protection
Protects the power unit from phase loss.
Note:
This parameter is only available in models 4A0930, 4A1200, and A1000 HHP.
No.
L8-78
Setting 0: Disabled
Setting 1: Enabled
n
L8-86: Detection Selection when Panel Fan Fails
Detects the loss of the drive panel fan by the panel fan input.
Note:
Settings 3 or 4 reduce inverter O/L level from 100% to 80%
No.
L8-86
Setting 0: Ramp Stop (Fault)
Setting 1: Coast Stop (Fault)
Setting 2: Fast Stop (Fault)
Setting 3: Continue Running (Alarm)
Setting 4: Continue Running at L8-19 Speed
Setting 5: Disabled
n
L8-87: Detection Selection when Diode Converter Fans Fail
Detects the loss of the Diode Converter fans by the fan control input.
Note:
Settings 3 or 4 reduce drive O/L level from 100% to 80%
No.
L8-87
Detection Selection when Diode Converter Fans Fail
Setting 0: Ramp Stop (Fault)
Setting 1: Coast Stop (Fault)
Setting 2: Fast Stop (Fault)
Setting 3: Continue Running (Alarm)
Setting 4: Continue Running at L8-19 Speed
Setting 5: Disabled
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Name
Power Unit Output Phase Loss Protection
Name
Detection selection when Panel Fan Fails
Name
1.8 L: Protection Functions
Setting Range
0, 1
Setting Range
0 to 5
Setting Range
0 to 5
Default
1
Default
1
Default
1
1
157