1.7 H: Terminal Functions
Frequency
Detection 4
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 145
Setting 1A: During Reverse
A digital output set for "During reverse" closes when the drive is running the motor in the reverse direction.
Status
Open
Motor is being driven in the forward direction or stopped.
Closed
Motor is being driven in reverse.
Setting 1B: During Baseblock (N.C.)
The output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not switch
and no main circuit voltage is output.
Status
Open
Baseblock is being executed.
Closed
Drive is not in a baseblock state.
Setting 1C: Motor 2 Selection
Indicates which motor is selected when another output terminal is set to switch drive operation between two motors (H1-
oo = 16).
Refer to Setting 16: Motor 2 Selection on page 100
Status
Open
Motor 1 is selected.
Closed
Motor 2 is selected.
Setting 1D: During Regeneration
Terminal closes when the motor is driven in the regenerative mode.
Setting 1E: Restart Enabled
An output set for "Restart enabled" closes when the drive attempts to restart after a fault has occurred.
112
Output Frequency
OFF
ON
Figure 1.71 Frequency Detection 4 Example with Positive L3-04 Value
Output frequency
FWD Run command
REV Run command
During Reverse
Figure 1.72 Reverse Direction Output Example Time Chart
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
L4-04
L4-03
Description
ON
OFF
Description
for details on switching motors.
Description
for more details.