L8-03: Overheat Pre-Alarm Operation Selection
Sets the operation when an overheat pre-alarm is detected.
Note:
Change L8-03 setting only when necessary.
No.
L8-03
Setting 0: Ramp to Stop
If an overheat alarm occurs, the drive decelerates to stop using the currently selected deceleration time. If a digital output is
programmed for "fault" (H2-oo = E), this output will be triggered.
Setting 1: Coast to Stop
If an overheat alarm occurs, the drive switches off the output and the motor coasts to stop. If a digital output is programmed
for "fault" (H2-oo = E), this output will be triggered.
Setting 2: Fast Stop
If an overheat alarm occurs, the drive decelerates to stop using the Fast Stop time (C1-09). If a digital output is programmed
for "fault" (H2-oo = E), this output will be triggered.
Setting 3: Alarm Only
If an overheat alarm occurs, an alarm is output and the drive continues operation.
Setting 4: Operation with Reduced Speed
If an overheat alarm occurs, the operation continues with the speed reduced to the level set to parameter L8-19. If the oH alarm
is still present after 10 s, the speed is reduced again. The amount of speed reduction depends on how often the alarm repeats.
If the oH alarm disappears while the drive is operating at a reduced speed, the drive will switch to the previous speed in 10 s
increments until reaching base frequency.
digital output programmed for 4D is switched when the oH alarm is still active after ten reduction cycles.
Output frequency
f
ref
f
× (L8-19)
ref
f
× (L8-19)
2
ref
f
× (L8-19)
3
ref
f
× (L8-19)
4
ref
oH alarm number
Digital output (4D)
n
L8-19: Frequency Reduction Rate during Overheat Pre-Alarm
Specifies the output frequency reduction when L8-03 is set to 4 and an oH alarm is present.
No.
L8-19
Frequency Reduction Rate During Overheat Pre-Alarm
n
L8-05: Input Phase Loss Protection Selection
Enables or disables the input phase loss detection.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Name
Overheat Pre-Alarm Operation Selection
Figure 1.105
10 s
10 s
10 s
oH
Alarm
oH
Alarm
oH
Alarm
Figure 1.105 Output Frequency Reduction During Overheat Alarm
Name
explains the operation with reduced speed during an oH alarm. A
10 s
10 s
10 s
Reset oH
Alarm
Reset oH
Alarm
1.8 L: Protection Functions
Setting Range
0 to 4
10 s
oH
etc.
Alarm
time
Setting Range
0.1 to 0.9
Default
3
1
Default
0.8
153