YASKAWA A1000 HHP Programming Manual page 277

High performance vector control drive
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
H3-09
Terminal A2 Signal Level
(417)
Selection
H3-10
Terminal A2 Function
(418)
Selection
H3-11
(419)
Terminal A2 Gain Setting
H3-12
(41A)
Terminal A2 Bias Setting
H3-13
Analog Input Filter Time
(41B)
Constant
H3-14
Analog Input Terminal
(41C)
Enable Selection
H3-16
Terminal A1 Offset
(2F0)
H3-17
Terminal A2 Offset
(2F1)
H3-18
Terminal A3 Offset
(2F2)
H3-oo
Function
Setting
0
Frequency bias
1
Frequency gain
Auxiliary frequency reference 1
2
(used as a Multi-Step Speed 2)
Auxiliary frequency reference 2
3
(3rd step analog)
4
Output voltage bias
5
Accel/decel time gain
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Description
All Modes
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note:
Use DIP switch S1 to set input terminal A2 for a current or a
voltage input signal.
All Modes
Sets the function of terminal A2.
All Modes
Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input
at terminal A2.
All Modes
Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is
input at terminal A2.
All Modes
Sets a primary delay filter time constant for terminals A1, A2, and A3. Used
for noise filtering.
All Modes
Determines which analog input terminals will be enabled when a digital input
programmed for "Analog input enable" (H1-oo = C) is activated.
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
All Modes
Adds an offset when the analog signal to terminal A1 is at 0 V.
All Modes
Adds an offset when the analog signal to terminal A2 is at 0 V.
All Modes
Adds an offset when the analog signal to terminal A3 is at 0 V.
H3 Multi-Function Analog Input Settings
All Modes
10 V = E1-04 (maximum output frequency)
All Modes
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting of -100
to 0%.
All Modes
10 V = E1-04 (maximum output frequency)
All Modes
10 V = E1-04 (maximum output frequency)
V/f
V/f
V/f w PG
V/f w PG
OLV/PM
AOLV/PM
10 V = E1-05 (motor rated voltage)
All Modes
10 V = 100%
A.9 H Parameters: Multi-Function Terminals
Description
OLV
CLV
CLV/PM
Values
Page
Default: 2
117
Range: 0 to 3
Default: 0
117
Range: 0 to 31
Default: 100.0%
Min.: -999.9
117
Max.: 999.9
Default: 0.0%
Min.: -999.9
117
Max.: 999.9
Default: 0.03 s
Min.: 0.00
117
Max.: 2.00
Default: 7
118
Range: 1 to 7
Default: 0
Min.: -500
118
Max.: 500
Default: 0
Min.: -500
118
Max.: 500
Default: 0
Min.: -500
118
Max.: 500
Page
118
119
119
119
119
119
277
A