T1-04: Motor Rated Current
Sets the motor rated current according to the motor nameplate value. Set the motor rated current between 50% and 100% of
the drive rated current for optimal performance in OLV or CLV. Enter the current at the motor base speed.
No.
T1-04
n
T1-05: Motor Base Frequency
Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used or
the motor is used in the field weakening area, enter the maximum frequency to E1-04 (E3-04 for motor 2) after Auto-Tuning
is complete.
No.
T1-05
n
T1-06: Number of Motor Poles
Sets the number of motor poles according to the motor nameplate value.
No.
T1-06
n
T1-07: Motor Base Speed
Sets the motor rated speed according to the motor nameplate value. Enter the speed at base frequency when using a motor
with an extended speed range or if using the motor in the field weakening area.
No.
T1-07
n
T1-08: PG Number of Pulses Per Revolution
Sets the number of pulses from the PG encoder. Set the actual number of pulses for one full motor rotation.
No.
T1-08
Note:
T1-08 will only be displayed in CLV.
n
T1-09: Motor No-Load Current
Sets the no-load current for the motor. The default setting displayed is no-load current automatically calculated from the output
power set in T1-02 and the motor rated current set to T1-04. Enter the data listed on the motor test report. Leave this data at
the default setting if the motor test report is not available.
No.
T1-09
Note:
The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value
has two decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal
place (0.1 A) if the maximum applicable motor capacity is higher than 11 kW.
n
T1-10: Motor Rated Slip
Sets the rated slip for the motor. The default setting displayed is the rated slip for a Yaskawa motor calculated from the rated
power set in T1-02. Enter the data listed on the motor test report.
No.
T1-10
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Name
Motor Rated Current
Name
Motor Base Frequency
Name
Number of Motor Poles
Name
Motor Base Speed
Name
PG Number of Pulses Per Revolution
Name
Motor No-Load Current
Name
Motor Rated Slip
1.11 T: Motor Tuning
Setting Range
10 to 200% of drive rated
current
Setting Range
0.0 to 400.0 Hz
Setting Range
2 to 48
Setting Range
0 to 24000 r/min
Setting Range
1 to 60000 ppr
Setting Range
0 A to [T1-04]
(Max: 0 to 2999.9)
Setting Range
0.00 to 20.00 Hz
Default
o2-04
Default
60.0 Hz
Default
4
Default
1750 r/min
Default
1024 ppr
Default
1
Default
169