YASKAWA A1000 HHP Programming Manual page 106

High performance vector control drive
Table of Contents

Advertisement

1.7 H: Terminal Functions
Setting
C
Frequency Reference Loss
E
Fault
F
Through Mode
10
Minor Fault
11
Fault Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
During Reverse
1B
During Baseblock (N.C.)
1C
Motor 2 Selection
1D
During regeneration
1E
Restart Enabled
1F
Motor Overload Alarm (oL1)
20
Drive Overheat Pre-Alarm (oH)
22
Mechanical Weakening Detection
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Open
Drive is stopped.
Closed
A Run command is input or the drive is in deceleration or DC injection.
Setting 1: Zero Speed
Terminal closes when the output frequency or motor speed (CLV, CLV/PM) falls below the minimum output frequency set
to E1-09 or b2-01.
Status
Open
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Closed
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
Note:
In CLV and CLV/PM control modes, the zero speed level is defined by b2-01. In all other control modes, the zero speed level is the minimum
output frequency set to E1-09.
106
Function
OFF
ON
Run command
Baseblock
OFF
command
Output
frequency
OFF
ON
During Run
Figure 1.62 During Run Time Chart
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Page
Setting
109
2F
Maintenance Period
109
30
During Torque Limit
109
31
During Speed Limit
110
32
During Speed Limit in Torque Control
110
33
Zero Servo Complete
110
37
During Frequency Output
110
38
Drive Enabled
110
39
Watt Hour Pulse Output
111
3C
LOCAL/REMOTE Status
111
3D
During Speed Search
3E
PID Feedback Low
109
3F
PID Feedback High
109
4A
During KEB Operation
112
4C
During Fast Stop
112
4D
oH Pre-Alarm Time Limit
112
60
Internal Cooling Fan Alarm
112
90
DriveWorksEZ Digital Output 1
112
91
DriveWorksEZ Digital Output 2
113
92
DriveWorksEZ Digital Output 3
113
100 to 192 Functions 0 to 92 with Inverse Output
113
Description
ON
Description
Function
Page
113
113
113
113
113
113
114
114
114
114
114
114
114
114
114
114
114
114

Hide quick links: