1.7 H: Terminal Functions
NOTICE: Rapid deceleration can trigger an overvoltage fault. When faulted, the drive output shuts off, and the motor coasts. To avoid this
uncontrolled motor state and to ensure that the motor stops quickly and safely, set an appropriate Fast Stop time to C1-09.
Setting 16: Motor 2 Selection
The drive has the capability to control two induction motors independently. A second motor may be selected using a multi-
function digital input as shown in
Note:
The motor 2 selection function cannot be used with PM motors.
When switching between motor 1 and motor 2, the parameters used to control those motors also change. Below,
lists the parameters that correspond to each motor:
No.
C1-oo: Acceleration/Deceleration
Time
C3-oo : Motor Slip Compensation C3-01 to C3-04, C3-15
C4-oo: Motor Torque
Compensation
C5-oo: Speed Control (ASR)
E1-oo, E3-oo: V/f Pattern
E2-oo, E4-oo: Motor Parameters
F1-oo (PG Constant)
Note:
1. When using 2 motors, the motor overload protection selection (oL1) set to L1-01 applies to both motor 1 and motor 2.
2. Attempting to switch between motor 1 and motor 2 during run will trigger the rUn alarm.
3. There is a 500 ms delay when switching between motors equipped with a PG encoder for feedback.
4. The motor 2 selection function cannot be used with PM motors.
If a digital output is programmed for "Motor 2 selection" (H1-01, H1-02, or H1-03 = 1C), the motor will be selected when
the output is closed.
Setting 18: Timer Function Input
This setting configures a digital input terminal as the input for the timer function. Use this setting combination with the timer
function output (H2-oo = 12).
100
Run/Stop
Fast-Stop
H1-
= 17
ON
Output Frequency
Figure 1.57 Fast Stop Sequence
Figure
1.58.
Drive
Motor switch input
Figure 1.58 Motor Selection
Table 1.38 Parameters for Switching Between Two Motors
Setting 16 Open (Motor 1)
C1-01 to C1-04
C4-01
C5-01 to C5-08, C5-12, C5-15
E1-oo, E2-oo
F1-01 to F1-21
Refer to b4: Timer Function on page 33
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
ON
ON
Decelerates at C1-09
for details.
ON
TIME
M
Motor 1
M
Motor 2
Setting 16 Closed (Motor 2)
C1-05 to C1-08
C3-21 to C3-25
C4-07
C5-21 to C5-28, C5-32, C5-35
E3-oo to E4-oo
F1-02 to F1-04, F1-08 to F1-11, F1-14,
F1-31 to F1-37
Table 1.38