o2-02: STOP Key Function Selection
Determines if the STOP key on the digital operator will stop drive operation when the drive is controlled from a remote source
(i.e., not from digital operator).
No.
o2-02
Setting 0: Disabled
Setting 1: Enabled
The STOP key will terminate drive operation even if the Run command source is not assigned to the digital operator. Cycle
the Run command to restart the drive if the drive has been stopped by pressing the STOP key.
n
o2-03: User Parameter Default Value
After completely setting up drive parameters, save the values as user-set defaults with parameter o2-03. After saving the values,
parameter A1-03 (Initialize Parameters) will offer the choice of "1110: User Initialize". Selecting 1110 resets all parameters
to the user-set default values.
No.
o2-03
Setting 0: No Change (Awaiting Command)
Setting 1: Set User Initialize Values
The current parameter settings are saved as user-set default for a later User Initialization. Setting o2-03 to 1 and pressing the
ENTER key saves the values and returns the display to 0.
Setting 2: Clear User Initialize Values
All user-set defaults for "User Initialize" are cleared. Setting o2-03 to 2 and pressing the ENTER key erases the values and
returns the display to 0.
n
o2-04: Drive Model Selection
Set this parameter when replacing the control board or the terminal board.
ND/HD on page 310
for information on drive model selection.
NOTICE: Drive performance will suffer and protective functions will not operate properly if the correct drive capacity is not set to o2-04.
No.
o2-04
Note:
Change o2-04 setting only when necessary.
n
o2-05: Frequency Reference Setting Method Selection
Determines if the ENTER key must be pressed after changing the frequency reference using the digital operator while in the
Drive Mode.
No.
o2-05
Frequency Reference Setting Method Selection
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Table 1.43 LO/RE Key and b1-07
Switch from LOCAL to REMOTE
Not possible
Not possible
Will not run until a new Run command is
entered.
If a Run command is entered, the drive will start
running as soon as the LO/RE key is pushed to
change from LOCAL to REMOTE.
Name
STOP Key Function Selection
Refer to A1-03: Initialize Parameters on page 11
Name
User Parameter Default Value
Name
Drive Model Selection
Name
1.10 o: Operator Related Settings
Switch from REMOTE to LOCAL
Not possible
Not possible
Run not possible
Run not possible
Setting Range
0, 1
for details on drive initialization.
Setting Range
0 to 2
Refer to Defaults by Drive Model and Duty Rating
Setting Range
-
Setting Range
0, 1
Default
1
Default
0
Default
Determined by
drive capacity
1
Default
0
163

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents