YASKAWA A1000 HHP Programming Manual page 265

High performance vector control drive
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
F6-01
Communications Error
(3A2)
Operation Selection
F6-02
External Fault from Comm.
(3A3)
Option Detection Selection
F6-03
External Fault from Comm.
(3A4)
Option Operation Selection
F6-04
bUS Error Detection Time
(3A5)
Torque Reference/Torque
F6-06
Limit Selection from Comm.
(3A7)
Option
Multi-Step Speed Enable/
F6-07
Disable Selection when
(3A8)
NefRef/ComRef is Selected
F6-08
Reset Communication
(36A)
Parameters
<1>
F6-10
CC-Link Node Address
(3B6)
F6-11
CC-Link Communication
(3B7)
Speed
F6-14
CC-Link bUS Error Auto
(3BB)
Reset
F6-20
MECHATROLINK Station
(36B)
Address
F6-21
MECHATROLINK Frame
(36C)
Size
F6-22
MECHATROLINK Link
(36D)
Speed
F6-23
MECHATROLINK
(36E)
Monitor Selection (E)
F6-24
MECHATROLINK
(36F)
Monitor Selection (F)
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Description
All Modes
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
All Modes
0: Always detected.
1: Detection during run only.
All Modes
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
All Modes
Sets the delay time for error detection if a bus error occurs.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
0: Disabled. Torque reference/limit from option board disabled.
1: Enabled. Torque reference/limit from option board enabled.
All Modes
0: Multi-step reference disabled (same as F7)
1: Multi-step reference enabled (same as V7)
All Modes
0: Communication-related parameters (F6-oo) are not reset when the drive
is initialized using A1-03.
1: Reset all communication-related parameters (F6-oo) when the drive is
initialized using A1-03.
All Modes
Sets the node address if a CC-Link option is installed.
All Modes
0: 156 Kbps
1: 625 Kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
All Modes
0: Disabled
1: Enabled
All Modes
Sets the station address when the MECHATROLINK-II option has been
installed.
All Modes
0: 32 byte
1: 17 byte
All Modes
0: 10 Mbps
1: 4 Mbps
All Modes
Sets the MECHATROLINK-II monitor (E).
All Modes
Sets the MECHATROLINK-II monitor (F).
CLV
CLV
A.8 F: Options
Values
Page
Default: 1
90
Range: 0 to 3
Default: 0
90
Range: 0, 1
Default: 1
90
Range: 0 to 3
Default: 2.0 s
Min.: 0.0
91
Max.: 5.0
Default: 0
90
Range: 0, 1
Default: 0
90
Range: 0, 1
Default: 0
91
Range: 0, 1
Default: 0
Min.: 0
91
Max.: 64
Default: 0
91
Range: 0 to 4
Default: 0
91
Range: 0, 1
Default: 21
Min.: 20
Max.: 3F
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF
265