A.9 H Parameters: Multi-Function Terminals
H1-oo
Function
Setting
35
PID input level selection
Forward run command
40
(2-Wire sequence)
Reverse run command
41
(2-Wire sequence)
Run command
42
(2-Wire sequence 2)
FWD/REV command
43
(2-Wire sequence 2)
44
Offset frequency 1
45
Offset frequency 2
46
Offset frequency 3
47
Node setup
60
DC Injection Braking command
External Speed Search
61
command 1
External Speed Search
62
command 2
63
Field weakening
65
KEB Ride-Thru 1 (N.C.)
66
KEB Ride-Thru 1 (N.O.)
67
Communications test mode
6A
Drive enable
272
H1 Multi-Function Digital Input Selections
All Modes
Closed: Inverts the PID input signal.
All Modes
Open: Stop
Closed: Forward run
Note:
Cannot be set together with settings 42 or 43.
All Modes
Open: Stop
Closed: Reverse run
Note:
Cannot be set together with settings 42 or 43.
All Modes
Open: Stop
Closed: Run
Note:
Cannot be set together with settings 40 or 41.
All Modes
Open: Forward
Closed: Reverse
Note:
Determines motor direction, but does not issue a Run command. Cannot be set
together with settings 40 or 41.
All Modes
Closed: Adds d7-01 to the frequency reference.
All Modes
Closed: Adds d7-02 to the frequency reference.
All Modes
Closed: Adds d7-03 to the frequency reference.
All Modes
Closed: Node setup for SI-S3 enabled.
V/f
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Closed: Triggers DC Injection Braking.
V/f
V/f
V/f w PG
OLV
OLV
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
Closed: Activates Current Detection Speed Search from the maximum output frequency
(E1-04).
V/f
V/f
V/f w PG
OLV
OLV
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
Closed: Activates Current Detection Speed Search from the frequency reference.
V/f
V/f
V/f w PG
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.
All Modes
Open: KEB Ride-Thru 1 enabled.
All Modes
Closed: KEB Ride-Thru 1 enabled.
All Modes
Tests the MEMOBUS/Modbus RS-485/422 interface. Displays "PASS" if the test completes
successfully.
All Modes
Open: Drive disabled. If this input is opened during run, the drive will stop as specified by
b1-03.
Closed: Ready for operation.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Description
CLV
CLV
CLV
CLV
Page
102
102
102
103
103
103
103
103
103
103
103
103
103
103
103
103
104