A.15 U: Monitors
No.
(Addr.
Name
Hex)
U4-23
Communication Option
(7DF)
Card Reference
U4-32
Motor Temperature (NTC)
(7FB)
U4-35
UV Alarm Location
(1042)
Monitor
U4-36
OV Alarm Location
(1043)
Monitor
U4-37
oH Alarm Location
(1044)
Monitor
U4-38
FAn Alarm Location
(1045)
Monitor
U4-39
voF Alarm Location
(1046)
Monitor
U4-41
UnbC Current Max
(7FE)
Location Monitor
<1> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<2> The unit is 1 A in models CIMR-Ao4A0930 and 4A1200.
304
Description
All Modes
Displays drive control data set by an option card as a four-digit hexadecimal
number.
All Modes
Displays the motor temperature (NTC).
U4-32 will display "20 °C" when a multi-function analog input is not set
for motor thermistor input (H1-oo = 17H).
All Modes
Displays the module where the UV alarm occurred as a binary number.
Bit 0: Axis 1
Bit 1: Axis 2
Bit 2: Axis 3
Bit 3: Axis 4
Bit 4: Axis 5
All Modes
Displays the module where the OV alarm occurred as a binary number.
Bit 0: Axis 1
Bit 1: Axis 2
Bit 2: Axis 3
Bit 3: Axis 4
Bit 4: Axis 5
All Modes
Displays the module where the oH alarm occurred as a binary number.
Bit 0: Axis 1
Bit 1: Axis 2
Bit 2: Axis 3
Bit 3: Axis 4
Bit 4: Axis 5
Note:
This parameter is only available in models CIMR-
Ao4A0930, 4A1200, and A1000 HHP.
All Modes
Displays the module where the FAn alarm occurred as a binary number.
Bit 0: Axis 1
Bit 1: Axis 2
Bit 2: Axis 3
Bit 3: Axis 4
Bit 4: Axis 5
Note:
This parameter is only available in models CIMR-
Ao4A0930, 4A1200, and A1000 HHP.
All Modes
Displays the module where the voF alarm occurred as a binary number.
Bit 0: Axis 1
Bit 1: Axis 2
Bit 2: Axis 3
Bit 3: Axis 4
Bit 4: Axis 5
Note:
This parameter is only available in models CIMR-
Ao4A0930, 4A1200, and A1000 HHP.
All Modes
Displays the maximum UnbC current detected.
Bit 0: Axis 1
Bit 1: Axis 2
Bit 2: Axis 3
Bit 3: Axis 4
Bit 4: Axis 5
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Analog Output
Unit
Level
No signal output
available
No signal output
°C
available
No signal output
available
No signal output
available
No signal output
available
No signal output
available
No signal output
available
No signal output
0.10%
available