YASKAWA A1000 HHP Programming Manual page 76

High performance vector control drive
Table of Contents

Advertisement

1.5 E: Motor Parameters
Setting = 8
50 Hz
400
30
14
0
1.3 2.5
50
Frequency (Hz)
Setting = C
90 Hz
400
24
12
0
1.5 3
60
90
Frequency (Hz)
Setting a Custom V/f Pattern (Setting F: Default)
Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
n
V/f Pattern Settings E1-04 to E1-13
If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04
through E1-13. To create a new V/f pattern, set E1-03 to F.
pattern.
Note:
Certain E1-oo parameters might not be visible depending on the control mode.
No.
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
E1-12
E1-13
<1> Default setting is determined by the control mode.
<3> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.
<4> The drive changes these settings when Auto-Tuning is performed (Rotational Auto-Tuning, Stationary Auto-Tuning 1, 2).
<5> Parameter ignored when E1-11 and E1-12 are set to 0.0.
76
Table 1.34 High Starting Torque, Settings 8 to B
Setting = 9
50 Hz
400
40
18
0
1.3 2.5
50
Frequency (Hz)
Table 1.35 Constant Output, Settings C to F
Setting = D
120 Hz
400
24
12
0
1.5 3
60
120
Frequency (Hz)
Parameter Name
Maximum Output Frequency
Maximum Voltage
Base Frequency
Middle Output Frequency
Middle Output Frequency Voltage
Minimum Output Frequency
Minimum Output Frequency Voltage
Middle Output Frequency 2
Middle Output Frequency Voltage 2
Base Voltage
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Setting = A
60 Hz
400
30
14
0
1.5 3
60
Frequency (Hz)
Setting = E
150 Hz
400
24
12
0
1.5 3
60
150
Frequency (Hz)
Refer to V/f Pattern on page 77
Refer to Parameter List on page 235
Setting Range
40.0 to 150.0 Hz
0.0 to 510.0 V
0.0 to [E1-04]
0.0 to [E1-04]
0.0 to 510.0 V
0.0 to [E1-04]
0.0 to 510.0 V
0.0 to [E1-04]
0.0 to 510.0 V
0.0 to 510.0 V
Setting = B
60 Hz
400
40
22
0
1.5 3
60
Frequency (Hz)
Setting = F
60 Hz
460
27.6
13.8
0
1.5 3
60
Frequency (Hz)
Note: The values in this graph are
specific to 400 V class drives in
setting F. Multiply the values by
1.25 for 575 V class drives.
Multiply the values by 1.725 for
690 V class drives.
for an example custom V/f
for details.
Default
<1>
<3>
<1>
<1>
<1>
<3>
<1>
<1>
<3>
<1>
<5>
0.0 Hz
<3>
<4> <5>
0.0 V
<3>
<4>
0.0 V