1.3 C: Tuning
Characteristics
C6-01
Performance
Use Heavy Duty Rating for applications requiring a high
Application
overload tolerance with constant load torque, such as
extruders and conveyors.
Overload capability (oL2)
Stall Prevention during
Acceleration (L3-02)
Stall Prevention during
Run (L3-06)
Default Carrier Frequency
Note:
Changing the Duty Mode selection automatically changes the maximum size motor that the drive can run, sets the E2-oo parameters to
appropriate values (E4-oo for motor 2), and recalculates parameter settings determined by motor capacity (e.g., b8-04, L2-03).
n
C6-02: Carrier Frequency Selection
Sets the switching frequency of the drive output transistors. Changes to the switching frequency lower audible noise and reduce
leakage current.
No.
Parameter Name
C6-02
Carrier Frequency Selection
Setting
58
Table 1.26 Differences between Heavy Duty and Normal Duty
Heavy Duty Rating (HD)
0
Overload
150 %
Rated Load
100 %
0
Motor Speed
150% of drive rated Heavy Duty current for 60 s
150%
150%
2 kHz
C6–02
1
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
100 %
Use Normal Duty Rating for applications in which the torque
requirements drop along with the speed, such as fans and
pumps where a high overload tolerance is not required.
120% of drive rated Normal Duty current for 60 s
Setting Range
1
Normal Duty Rating (ND)
1
Overload
120 %
Rated Load
100 %
0
Motor Speed
120%
120%
2 kHz Swing PWM
Default
1
Carrier Frequency
2.0 kHz
100 %