Building Technologies
HVAC Products
9.2.3 Prepurging
This position is approached in phase Traveling to prepurging (24).
The position can be set via the following parameters:
Parameter
501.01
502.01
503.01
No.
Parameter
Gas: Prepurging
222
0 = inactive
1 = active
Oil: Prepurging
262
0 = inactive
1 = active
9.2.4 Ignition
The ignition position is approached in phase Traveling to the ignition position (38).
The position is set via curve parameterization under P0 . In modulating operation, this
point is assigned to an output of 10%.
9.2.5 Postpurging
This position is approached in phase Traveling to postpurging (72).
The position can be set via the following parameters:
Parameter
501.02
502.02
503.02
Basic documentation LMV37.4...
9 Electronic air-fuel ratio control
Actuator
Prepurge position fuel actuator
Prepurge position air actuator
Prepurge speed VSD
Actuator
Postpurge position fuel actuator
Postpurge position air actuator
Postpurge speed VSD
79/213
CC1P7546en
01.12.2009