3.4

Settings

GIN
Obj.-
Adr.
Group Entry
1
0
1201
50, 51 Phase Time Overcurrent
1
1
1217
50-3 Pickup
1
2
1218
50-3 Time Delay
1
3
1202
50-2 Pickup
1
4
1203
50-2 Time Delay
1
5
1204
50-1 Pickup
1
6
1205
50-1 Time Delay
1
7
1207
51 Pickup
1
8
1208
51 Time Delay
1
9
1209
51 Time Dial
1
10
1210
Drop-out characteristic
1
11
1211
IEC Curve
1
12
1212
ANSI Curve
1
13
1223
51V V< Threshold for Release Ip
7SJ61 / 7SJ62 / 7SJ64 Bus mapping
C53000-L2540-A306-2
Note
The settings which can be read and written are given in the following table. The setting
options are indicated in column "Generic identification data". If no values are indicated
the setting is a number. For the vaild setting range please refer to the user manual of
the device.
GIN = Generic Identification Number
For the position and format of the GIN within the telegram please refer to the official
IEC 60870-5-103 standard.
Name
Generic identification
data
22 ON
23 OFF
12964 Instantaneous
12965 Disk Emulation
12559 Normal Inverse
12560 Very Inverse
12561 Extremely Inv.
12837 Long Inverse
12808 Inverse
12809 Short Inverse
12810 Long Inverse
12811 Moderately Inv.
12812 Very Inverse
12813 Extremely Inv.
12814 Definite Inv.
24 NO
30013 Volt. controll.
30014 Volt. Restraint
Point List
Note
45