Modbus Register Map Organization
Register Designation of the SIPROTEC objects
10044
PhC InrushBlk
10045
INRUSH X-BLK
1.4.4

Registers 10046 to 10053: Directional Overcurrent Protection

Register Designation of the SIPROTEC objects
10046
67 ACTIVE
10047
67N ACTIVE
10048
67/67N pickedup
10049
67 A picked up
10050
67 B picked up
10051
67 C picked up
10052
67N picked up
10053
67/67N TRIP
1.4.5

Registers 10054 to 10058: Negative Sequence Protection

Register Designation of the SIPROTEC objects
10054
46 ACTIVE
10055
46-2 picked up
10056
46-1 picked up
10057
46-TOC pickedup
10058
46 TRIP
1.4.6

Registers 10059 to 10063: Frequency protection

Register Designation of the SIPROTEC objects
10059
81 ACTIVE
10060
81-1 picked up
10061
81-2 picked up
10062
81-1 TRIP
10063
81-2 TRIP
24
Comment
1 = Phase C trip blocked by inrush detection
1 = Cross blk: PhX blocked PhY
Comment
1 = 67/67-TOC is ACTIVE
1 = 67N/67N-TOC is ACTIVE
1 = 67/67N picked up
1 = 67/67-TOC Phase A picked up
1 = 67/67-TOC Phase B picked up
1 = 67/67-TOC Phase C picked up
1 = 67N/67N-TOC picked up
1 = 67/67N TRIP
Comment
1 = 46 is ACTIVE
1 = 46-2 picked up
1 = 46-1 picked up
1 = 46-TOC picked up
1 = 46 TRIP
Comment
1 = 81 is ACTIVE
1 = 81-1 picked up
1 = 81-2 picked up
1 = 81-1 TRIP
1 = 81-2 TRIP
SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80
Internal
object
no.
1842
1843
Internal
object
no.
2653
2658
2691
2692
2692
2693
2695
2696
Internal
object
no.
5153
5159
5165
5166
5170
Internal
object
no.
5213
5232
5233
5236
5237
C53000-L2240-A320-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sk80Siprotec 7rw80

Table of Contents