1.4.7
Registers 10064 to 10069: Under/Overvoltage Protection
Register Designation of the SIPROTEC objects
10064
27 ACTIVE
10065
27-1 picked up
10066
27-1 TRIP
10067
59 ACTIVE
10068
59-1 picked up
10069
59-1 TRIP
1.4.8
Registers 10070 to 10081: (Sensitive) Ground Fault Protection
Register Designation of the SIPROTEC objects
10070
50Ns/67Ns ACT
10071
64 Pickup
10072
64 TRIP
10073
50Ns-2 Pickup
10074
50Ns-2 TRIP
10075
50Ns-1 Pickup
10076
50Ns-1 TRIP
10077
Sens. Gnd Ph A
10078
Sens. Gnd Ph B
10079
Sens. Gnd Ph C
10080
SensGnd Forward
10081
SensGnd Reverse
1.4.9
Registers 10082 to 10083: Startup Counter for Motors
Register Designation of the SIPROTEC objects
10082
66 ACTIVE
10083
66 TRIP
SIPROTEC Modbus - Bus mapping 7SJ80/7SK80/7RW80
C53000-L2240-A320-3
Comment
1 = 27 Undervoltage protection is ACTIVE
1 = 27-1 Undervoltage picked up
1 = 27-1 Undervoltage TRIP
1 = 59-Overvoltage protection is ACTIVE
1 = 59 picked up
1 = 59 TRIP
Comment
1 = 50Ns/67Ns is ACTIVE
1 = 64 displacement voltage pick up
1 = 64 displacement voltage element TRIP
1 = 50Ns-2 Pickup
1 = 50Ns-2 TRIP
1 = 50Ns-1 Pickup
1 = 50Ns-1 TRIP
1 = Sensitive ground fault picked up in phase A
1 = Sensitive ground fault picked up in phase B
1 = Sensitive ground fault picked up in phase C
1 = Sensitive ground fault in forward direction
1 = Sensitive ground fault in reverse direction
Comment
1 = 66 Motor start protection is ACTIVE
1 = 66 Motor start protection TRIP
Modbus Register Map Organization
Internal
object
no.
6532
6533
6539
6567
6568
6570
Internal
object
no.
1212
1215
1217
1221
1223
1224
1226
1272
1273
1274
1276
1277
Internal
object
no.
4826
4827
25