4.8.3

Reduced acceptance test

A complete acceptance test is only necessary following first commissioning. An acceptance
test with a reduced scope is sufficient for expansions of safety functions.
The reduced acceptance tests must be carried out separately for each individual drive, as far
as the machine allows.
Table 4- 1
Reduced acceptance test for function extensions
Measure
Replacing the Control Unit or
the Power Modules.
Hardware replacement of
safety-related distributed I/O
devices (e.g. emergency off
switch).
Update the firmware of the
Control Unit.
Change to a single limit (e.g.
SLS limit).
Functional expansion of the
machine (additional drive).
Functional expansion of a
drive (e.g. additional SLS
limit).
Transfer of inverter
parameters to other identical
machines by means of
standard commissioning.
Safety Integrated Function Manual, SINAMICS G120
Function Manual, 07/2010, FW 4.3.2, A5E03052391B AA
Documentation
Supplement:
Hardware data
Configuration
Firmware Versions
Supplement:
Hardware data
Configuration
Firmware Versions
Supplement:
Version data
New safety functions
Supplement to the safety
functions for each drive.
Supplementary safety functions
for each drive and function table.
Supplement to the safety
functions for each drive and
function table.
Supplement to the machine
description (checking of the
firmware versions).
4.8 Acceptance test - Completion of commissioning
Acceptance test
Function test
Conclusion of the report
Yes.
Supplement:
New checksums and
countersignature
Partially.
No.
Limitation to
replaced
components.
Yes.
Supplement:
New checksums and
countersignature.
Partially.
Supplement:
Testing the changed
New checksums and
limit value.
countersignature.
Yes.
Supplement:
Testing the
New checksums and
additional functions.
countersignature.
Yes.
Supplement.
Test the additional
New checksums and
functions.
countersignature.
No.
No, if data are identical
(checking of checksums).
Commissioning