Reduced Acceptance After Component Replacement And Firmware Change - Siemens SINAMICS G120C Operating Instructions Manual

Low voltage converters
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

10.6
Reduced acceptance after component replacement and
firmware change
After a component has been replaced or the firmware updated, a reduced acceptance test of the
safety functions must be performed.
Measure
Replacing the converter with an
identical type
Replacing the motor with an identi‐
cal pole pair number
Replace the gearbox with an identi‐
cal ratio
Replacing safety-related I/O devices
(e.g. Emergency Stop switch).
Converter firmware update.
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
10.6 Reduced acceptance after component replacement and firmware change
Acceptance test
No.
Only check the direction of ro‐
tation of the motor.
No.
Only check the control of the
safety functions affected by
the components that have
been replaced.
No.
Corrective maintenance
Reduced acceptance test
Documentation
Supplement the converter data
Log the new checksums
Countersignature
Supplement the hardware ver‐
sion in the converter data.
No change.
 
No change.
Supplement firmware version
in the converter data
Log the new checksums
Countersignature.
417

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120c uss/mbSinamics g120c dpSinamics g120c pn

Table of Contents