Reduced acceptance test after expanding the function

A full acceptance test is necessary only after first commissioning. A reduced acceptance test
is sufficient when safety functions are expanded.
Table 5-1
Measure
Changing a single limit
(e.g. SLS level).
Functional expansion of
the machine (additional
drive).
Functional expansion of a
drive (e.g. additional SLS
level or new safety func‐
tion following a firmware
update).
Transfer of inverter set‐
tings to other identical ma‐
chines by means of series
commissioning.
The inverter changes the following parameters after changing the settings of the safety functions:
1)
- checksum r9781
- time stamp r9782
(Page 366)
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
Reduced acceptance test after expanding the function
Acceptance test
Check the modified lim‐
it value.
Check the safety func‐
tions of the new drive.
Check the additional
functions.
Check the control and
feedback signal of all
safety functions.
Reduced acceptance after a component has been replaced and a firmware change
5.17 Acceptance tests for the safety functions
Documentation
● Supplement function table
● Log modified settings
● Document the changed checksum and time
stamp
1)
● Countersignature
● Supplement machine overview
● Supplement article number and firmware
version of the drive
● Supplement function table
● Log the settings of the new drive
● Document the changed checksum and time
stamp
1)
● Countersignature
● Supplement function table
● Log modified settings
● Document the changed checksum and time
stamp
1)
● Countersignature
● Supplement machine description
● Log modified settings
● Check the changed checksum and time
stamp
1)
● Check the firmware versions
Commissioning