8.10.8.3

Reduced acceptance test

A complete acceptance test is only necessary following first commissioning. An acceptance
test with a reduced scope is sufficient for expansions of safety functions.
The reduced acceptance tests must be carried out separately for each individual drive, as far
as the machine allows.
Table 8- 40
Reduced acceptance test for function extensions
Measure
Replace the inverter.
Replace the motor
Replace the gear unit
Replace the safety-related
peripherals (e.g. Emergency
Off switch).
Inverter firmware update.
Functional expansion of the
machine (additional drive).
Transfer of inverter
parameters to other identical
machines by means of series
commissioning.
SINAMICS G120C Inverter
Operating Instructions, 01/2011, FW 4.4, A5E02999804A AB
Documentation
Supplement:
Inverter data
No
No
No
Supplement:
Firmware version in the
inverter data
Supplement:
Machine overview
Inverter data
Function table
Limit values
Supplement to the machine
description (checking of the
firmware versions).
8.10 Fail-safe function Safe Torque Off (STO)
Acceptance test
Function test
Yes
Partially.
Test the safety function
SDI.
Yes
Partially.
Limitation to replaced
components.
Yes
Yes
Testing the additional
functions.
No
Functions
Conclusion of the report
Supplement:
New checksums and
countersignature
No
No
No
Supplement:
New checksums and
countersignature.
Supplement:
New checksums and
countersignature.
No, if data are identical
(checking of checksums).