3.3.13 Checking the Temperature Measurement via RTD-Box

SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Figure 3-39
Polarity testing for I
Holmgreen-connection (VTs Wye-connected)
After the termination of the RS485 port and the setting of the bus address have been
verified according to Section 3.2, the measured temperature values and thresholds
can be checked.
If temperature sensors are used with 2-phase connection you must first determine the
line resistance for the temperature detector being short-circuited. Select mode 6 at the
RTD-Box and enter the resistance value you have determined for the corresponding
sensor (range: 0 to 50.6 Ω).
When using the preset 3-phase connection for the temperature detectors no further
entry must be made.
For checking the measured temperature values, the temperature detectors are re-
placed by adjustable resistors (e.g. precision resistance decade) and the correct as-
signment of the resistance value and the displayed temperature for 2 or 3 temperature
values from the following table are verified.
Table 3-37
Assignment of the resistance value and the temperature of the sensors
Temperature in
Temperature in
°C
–50
–58
–40
–40
–30
–22
–20
–4
–10
14
0
32
10
50
20
68
, example with current transformers configured in a
N
Ni 100 DIN 43760 Ni 120 DIN 34760 Pt 100 IEC 60751
°F
74.255
79.1311726
84.1457706
89.2964487
94.581528
100
105.551528
111.236449
3.3 Commissioning
89.106
80.3062819
94.9574071
84.270652
100.974925
88.2216568
107.155738
92.1598984
113.497834
96.085879
120
100
126.661834
103.902525
133.483738
107.7935