3 Mounting and Commissioning
Power Supply
Pickup Voltages of
BI1 to BI3
379
Table 3-2
Jumper settings for the nominal voltage of the integrated power supply on the
processor board A–CPU for 7SJ62.../DD
Jumper
60 to 125 VDC
X51
1-2
X52
1-2 and 3-4
X53
1-2
Table 3-3
Jumper settings of control voltages of binary inputs BI1 to BI3 on the processor
board A–CPU for 7SJ62.../DD
Binary Inputs
BI1
BI2
BI3
1)
Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 VDC to 220 VDC and 115/230
VAC
Rated Voltage
110 to 250 VDC
115 VAC
2-3
2-3
2-3
interchangeable
Jumper
19 VDC Pickup
X21
X22
X23
24/48 VDC
230 VAC
Jumpers X51 to X53 are not used
cannot be changed
1)
88 VDC Pickup
L
H
L
H
L
H
SIPROTEC 4, 7SJ62/63/64 Handbuch