2.13.3 Settings

Addr.
Parameter
3301
INTERM.EF
3302
Iie>
3302
Iie>
3302
Iie>
3303
T-det.ext.
3304
T-sum det.
3305
T-reset
3306
Nos.det.

2.13.4 Information List

No.
Information
6903
>IEF block
6921
IEF OFF
6922
IEF blocked
6923
IEF enabled
6924
IIE Fault det
6925
IIE stab.Flt
6926
IIE Flt.det FE
6927
Intermitt.EF
6928
IEF Tsum exp.
6929
IEF Tres run.
6930
IEF Trip
6931
Iie/In=
6932
Nos.IIE=
227
The table indicates region-specific default settings. Column C (configuration) indicates
the corresponding secondary nominal current of the current transformer.
C
Setting Options
OFF
ON
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
0.005 .. 1.500 A
0.00 .. 10.00 sec
0.00 .. 100.00 sec
1 .. 600 sec
2 .. 10
Type of In-
formation
SP
OUT
OUT
OUT
OUT
OUT
OUT
OUT
OUT
OUT
OUT
VI
VI
Default Setting
OFF
1.00 A
5.00 A
1.00 A
5.00 A
1.000 A
0.10 sec
20.00 sec
300 sec
3
Comments
>block interm. E/F prot.
Interm. E/F prot. is switched off
Interm. E/F prot. is blocked
Interm. E/F prot. is active
Interm. E/F detection stage Iie>
Interm. E/F stab detection
Interm.E/F det.stage Iie> f.Flt. ev.Prot
Interm. E/F detected
Counter of det. times elapsed
Interm. E/F: reset time running
Interm. E/F: trip
Max RMS current value of fault =
No. of detections by stage Iie>=
C53000-G1140-C147-A, Edition 07.2015
Comments
Intermittent earth fault pro-
tection
Pick-up value of interm.
E/F stage
Pick-up value of interm.
E/F stage
Pick-up value of interm.
E/F stage
Detection extension time
Sum of detection times
Reset time
No. of det. for start of int.
E/F prot