Settings; Information List - Siemens siprotec SJ62 User Manual

Multi-functional protective relay with local control
Table of Contents

Advertisement

2 Functions
2.1.4.3

Settings

Addr.
Parameter
401
WAVEFORMTRIGGE
R
402
WAVEFORM DATA
403
MAX. LENGTH
404
PRE. TRIG. TIME
405
POST REC. TIME
406
BinIn CAPT.TIME
2.1.4.4

Information List

No.
Information
-
FltRecSta
4
>Trig.Wave.Cap.
203
Wave. deleted
30053
Fault rec. run.
51
The actual storage time encompasses the pre-fault time PRE. TRIG. TIME (address
404) ahead of the reference instant, the normal recording time and the post-fault time
POST REC. TIME (address 405) after the storage criterion has reset. The maximum
length of a fault record MAX. LENGTH is entered in Address 403. The saving of each
fault record must not exceed five seconds. A total of 8 records can be saved. However,
the total length of time of all fault records in the buffer may not exceed 5 seconds.
An oscillographic record can be triggered by a change in status of a binary input, or
through the operating interface via PC. Storage is then triggered dynamically. The
length of the fault recording is set in address 406 BinIn CAPT.TIME (maximum
length however is MAX. LENGTH, address 403). Pre-fault and post-fault times will be
included. If the binary input time is set for ∞, then the length of the record equals the
time that the binary input is activated (static), or the MAX. LENGTH setting in address
403, whichever is shorter.
Setting Options
Save w. Pickup
Save w. TRIP
Start w. TRIP
Fault event
Pow.Sys.Flt.
0.30 .. 5.00 sec
0.05 .. 0.50 sec
0.05 .. 0.50 sec
0.10 .. 5.00 sec; ∞
Type of In-
formation
IntSP
SP
OUT_Ev
OUT
Default Setting
Save w. Pickup
Fault event
2.00 sec
0.25 sec
0.10 sec
0.50 sec
Comments
Fault Recording Start
>Trigger Waveform Capture
Waveform data deleted
Fault recording is running
C53000-G1140-C147-A, Edition 07.2015
Comments
Waveform Capture
Scope of Waveform Data
Max. length of a Waveform
Capture Record
Captured Waveform Prior to
Trigger
Captured Waveform after Event
Capture Time via Binary Input
SIPROTEC 4, 7SJ62/63/64 Handbuch