A.8
Settings
Addr.
Parameter
201
CT Starpoint
202
Vnom PRIMARY
203
Vnom SECONDARY
204
CT PRIMARY
205
CT SECONDARY
206A
Vph / Vdelta
209
PHASE SEQ.
210A
TMin TRIP CMD
211A
TMax CLOSE CMD
212
BkrClosed I MIN
213
VT Connect. 3ph
214
Rated Frequency
215
Distance Unit
217
Ignd-CT PRIM
218
Ignd-CT SEC
235A
ATEX100
240
VT Connect. 1ph
250A
50/51 2-ph prot
260
Ir-52
261
OP.CYCLES AT Ir
262
Isc-52
263
OP.CYCLES Isc
264
Ix EXPONENT
265
Cmd.via control
266
T 52 BREAKTIME
267
T 52 OPENING
276
TEMP. UNIT
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Addresses which have an appended "A" can only be changed with DIGSI, under "Dis-
play Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates
the corresponding secondary nominal current of the current transformer.
Function
C
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
1A
5A
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
P.System Data 1
Setting Options
towards Line
towards Line
towards Busbar
0.10 .. 800.00 kV
12.00 kV
100 .. 225 V
100 V
10 .. 50000 A
100 A
1A
1A
5A
1.00 .. 3.00
1.73
A B C
A B C
A C B
0.01 .. 32.00 sec
0.15 sec
0.01 .. 32.00 sec
1.00 sec
0.04 .. 1.00 A
0.04 A
0.20 .. 5.00 A
0.20 A
Van, Vbn, Vcn
Van, Vbn, Vcn
Vab, Vbc, VGnd
Van,Vbn,Vcn,VGn
Van,Vbn,Vcn,VSy
50 Hz
50 Hz
60 Hz
km
km
Miles
1 .. 50000 A
60 A
1A
1A
5A
NO
NO
YES
NO
NO
Van
Vbn
Vcn
Vab
Vbc
Vca
ON
OFF
OFF
10 .. 50000 A
125 A
100 .. 1000000
10000
10 .. 100000 A
25000 A
1 .. 1000
50
1.0 .. 3.0
2.0
(Setting options depend
None
on configuration)
1 .. 600 ms
80 ms
1 .. 500 ms
65 ms
Celsius
Celsius
Fahrenheit
Default Setting
CT Starpoint
Rated Primary Voltage
Rated Secondary Voltage (L-L)
CT Rated Primary Current
CT Rated Secondary Current
Matching ratio Phase-VT To
Open-Delta-VT
Phase Sequence
Minimum TRIP Command Dura-
tion
Maximum Close Command Du-
ration
Closed Breaker Min. Current
Threshold
VT Connection, three-phase
Rated Frequency
Distance measurement unit
Ignd-CT rated primary current
Ignd-CT rated secondary current
Storage of th. Replicas w/o
Power Supply
VT Connection, single-phase
50, 51 Time Overcurrent with
2ph. prot.
Rated Normal Current (52 Break-
er)
Switching Cycles at Rated
Normal Current
Rated Short-Circuit Breaking
Current
Switch. Cycles at Rated Short-
Cir. Curr.
Exponent for the Ix-Method
52 B.Wear: Open Cmd. via
Control Device
Breaktime (52 Breaker)
Opening Time (52 Breaker)
Unit of temperature measure-
ment
A.8 Settings
Comments
644