Settings; Information List - Siemens siprotec SJ62 User Manual

Multi-functional protective relay with local control
Table of Contents

Advertisement

2 Functions
2.1.6.3

Settings

Addr.
Parameter
1101
FullScaleVolt.
1102
FullScaleCurr.
1103
RG/RL Ratio
1104
XG/XL Ratio
1105
x'
1106
x'
1107
I MOTOR START
1108
P,Q sign
2.1.6.4

Information List

No.
Information
126
ProtON/OFF
356
>Manual Close
501
Relay PICKUP
511
Relay TRIP
533
Ia =
534
Ib =
535
Ic =
561
Man.Clos.Detect
2720
>Enable ANSI#-2
4601
>52-a
4602
>52-b
16019
>52 Wear start
16020
52 WearSet.fail
16027
52WL.blk I PErr
16028
52WL.blk n PErr
57
The table indicates region-specific default settings. Column C (configuration) indicates
the corresponding secondary nominal current of the current transformer.
C
Setting Options
0.10 .. 800.00 kV
10 .. 50000 A
-0.33 .. 7.00
-0.33 .. 7.00
0.0050 .. 15.0000 Ω/mi
1A
0.0010 .. 3.0000 Ω/mi
5A
0.0050 .. 9.5000 Ω/km
1A
0.0010 .. 1.9000 Ω/km
5A
1A
0.40 .. 10.00 A
5A
2.00 .. 50.00 A
not reversed
reversed
Type of In-
formation
IntSP
SP
OUT
OUT
VI
VI
VI
OUT
SP
SP
SP
SP
OUT
OUT
OUT
Default Setting
12.00 kV
100 A
1.00
1.00
0.2420 Ω/mi
0.0484 Ω/mi
0.1500 Ω/km
0.0300 Ω/km
2.50 A
12.50 A
not reversed
Comments
Protection ON/OFF (via system port)
>Manual close signal
Relay PICKUP
Relay GENERAL TRIP command
Primary fault current Ia
Primary fault current Ib
Primary fault current Ic
Manual close signal detected
>Enable 50/67-(N)-2 (override 79 blk)
>52-a contact (OPEN, if bkr is open)
>52-b contact (OPEN, if bkr is closed)
>52 Breaker Wear Start Criteria
52 Wear blocked by Time Setting Failure
52 Breaker Wear Logic blk Ir-CB>=Isc-CB
52 Breaker W.Log.blk SwCyc.Isc>=SwCyc.Ir
C53000-G1140-C147-A, Edition 07.2015
Comments
Measurem:FullScaleVolt-
age(Equipm.rating)
Measurem:FullScaleCur-
rent(Equipm.rating)
RG/RL - Ratio of Gnd to
Line Resistance
XG/XL - Ratio of Gnd to
Line Reactance
x' - Line Reactance per
length unit
x' - Line Reactance per
length unit
Motor Start Current (Block
49, Start 48)
P,Q operational measured
values sign
SIPROTEC 4, 7SJ62/63/64 Handbuch

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec sj63Siprotec sj64

Table of Contents