Settings; Information List - Siemens siprotec SJ62 User Manual

Multi-functional protective relay with local control
Table of Contents

Advertisement

2.9.3

Settings

Addr.
Parameter
5401
FCT 81 O/U
5402
Vmin
5403
81-1 PICKUP
5404
81-1 PICKUP
5405
81-1 DELAY
5406
81-2 PICKUP
5407
81-2 PICKUP
5408
81-2 DELAY
5409
81-3 PICKUP
5410
81-3 PICKUP
5411
81-3 DELAY
5412
81-4 PICKUP
5413
81-4 PICKUP
5414
81-4 DELAY
2.9.4

Information List

No.
Information
5203
>BLOCK 81O/U
5206
>BLOCK 81-1
5207
>BLOCK 81-2
5208
>BLOCK 81-3
5209
>BLOCK 81-4
5211
81 OFF
5212
81 BLOCKED
5213
81 ACTIVE
5214
81 Under V Blk
5232
81-1 picked up
5233
81-2 picked up
5234
81-3 picked up
5235
81-4 picked up
5236
81-1 TRIP
5237
81-2 TRIP
5238
81-3 TRIP
5239
81-4 TRIP
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Setting Options
OFF
ON
10 .. 150 V
45.50 .. 54.50 Hz
55.50 .. 64.50 Hz
0.00 .. 100.00 sec; ∞
45.50 .. 54.50 Hz
55.50 .. 64.50 Hz
0.00 .. 100.00 sec; ∞
45.50 .. 54.50 Hz
55.50 .. 64.50 Hz
0.00 .. 100.00 sec; ∞
45.50 .. 54.50 Hz
55.50 .. 64.50 Hz
0.00 .. 100.00 sec; ∞
Type of In-
formation
SP
>BLOCK 81O/U
SP
>BLOCK 81-1
SP
>BLOCK 81-2
SP
>BLOCK 81-3
SP
>BLOCK 81-4
OUT
81 OFF
OUT
81 BLOCKED
OUT
81 ACTIVE
OUT
81 Under Voltage Block
OUT
81-1 picked up
OUT
81-2 picked up
OUT
81-3 picked up
OUT
81-4 picked up
OUT
81-1 TRIP
OUT
81-2 TRIP
OUT
81-3 TRIP
OUT
81-4 TRIP
2.9 Frequency Protection 81 O/U
Default Setting
OFF
81 Over/Under Frequency Protec-
tion
65 V
Minimum required voltage for op-
eration
49.50 Hz
81-1 Pickup
59.50 Hz
81-1 Pickup
60.00 sec
81-1 Time Delay
49.00 Hz
81-2 Pickup
59.00 Hz
81-2 Pickup
30.00 sec
81-2 Time Delay
47.50 Hz
81-3 Pickup
57.50 Hz
81-3 Pickup
3.00 sec
81-3 Time delay
51.00 Hz
81-4 Pickup
61.00 Hz
81-4 Pickup
30.00 sec
81-4 Time delay
Comments
Comments
174