Motor (Motor Starting Protection 48, Motor Restart Inhibit 66); Settings - Siemens siprotec SJ62 User Manual

Multi-functional protective relay with local control
Table of Contents

Advertisement

2 Functions
2.8.3

Motor (Motor Starting Protection 48, Motor Restart Inhibit 66)

2.8.3.1

Settings

Addr.
Parameter
4101
FCT 48/66
4102
STARTUP CURRENT
4103
STARTUP TIME
4104
LOCK ROTOR TIME
4301
FCT 66
4302
IStart/IMOTnom
4303
T START MAX
4304
T Equal
4305
I MOTOR NOMINAL
4306
MAX.WARM STARTS
4307
#COLD-#WARM
4308
Kτ at STOP
4309
Kτ at RUNNING
4310
T MIN. INHIBIT
169
Functions Motor Starting Protection and Restart Inhibit for Motors associated with
motor protection are described in the previous two sections and contain information
concerning configuration.
The table indicates region-specific default settings. Column C (configuration) indicates
the corresponding secondary nominal current of the current transformer.
C
Setting Options
OFF
ON
1A
0.50 .. 16.00 A
5A
2.50 .. 80.00 A
1.0 .. 180.0 sec
0.5 .. 120.0 sec; ∞
OFF
ON
1.10 .. 10.00
3 .. 320 sec
0.0 .. 320.0 min
1A
0.20 .. 1.20 A
5A
1.00 .. 6.00 A
1 .. 4
1 .. 2
0.2 .. 100.0
0.2 .. 100.0
0.2 .. 120.0 min
Default Setting
OFF
48 / 66 Motor (Startup
Monitor/Counter)
5.00 A
Startup Current
25.00 A
10.0 sec
Startup Time
2.0 sec
Permissible Locked Rotor
Time
OFF
66 Startup Counter for
Motors
4.90
I Start / I Motor nominal
10 sec
Maximum Permissible
Starting Time
1.0 min
Temperature Equalizaton
Time
1.00 A
Rated Motor Current
5.00 A
2
Maximum Number of
Warm Starts
1
Number of Cold Starts -
Warm Starts
5.0
Extension of Time Con-
stant at Stop
2.0
Extension of Time Con-
stant at Running
6.0 min
Minimum Restart Inhibit
Time
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015