2 Functions
Addr.
Parameter
5113A
27-1 DOUT RATIO
5114A
27-2 DOUT RATIO
5120A
CURRENT SUPERV.
2.6.6

Information List

No.
Information
234.2100 27, 59 blk
6503
>BLOCK 27
6505
>27 I SUPRVSN
6506
>BLOCK 27-1
6508
>BLOCK 27-2
6513
>BLOCK 59-1
6530
27 OFF
6531
27 BLOCKED
6532
27 ACTIVE
6533
27-1 picked up
6534
27-1 PU CS
6537
27-2 picked up
6538
27-2 PU CS
6539
27-1 TRIP
6540
27-2 TRIP
6565
59 OFF
6566
59 BLOCKED
6567
59 ACTIVE
6568
59-1 picked up
6570
59-1 TRIP
6571
59-2 picked up
6573
59-2 TRIP
145
Setting Options
1.01 .. 3.00
1.01 .. 3.00
OFF
ON
Type of In-
formation
IntSP
27, 59 blocked via operation
SP
>BLOCK 27 undervoltage protection
SP
>27-Switch current supervision ON
SP
>BLOCK 27-1 Undervoltage protection
SP
>BLOCK 27-2 Undervoltage protection
SP
>BLOCK 59-1 overvoltage protection
OUT
27 Undervoltage protection switched OFF
OUT
27 Undervoltage protection is BLOCKED
OUT
27 Undervoltage protection is ACTIVE
OUT
27-1 Undervoltage picked up
OUT
27-1 Undervoltage PICKUP w/curr. superv
OUT
27-2 Undervoltage picked up
OUT
27-2 Undervoltage PICKUP w/curr. superv
OUT
27-1 Undervoltage TRIP
OUT
27-2 Undervoltage TRIP
OUT
59-Overvoltage protection switched OFF
OUT
59-Overvoltage protection is BLOCKED
OUT
59-Overvoltage protection is ACTIVE
OUT
59 picked up
OUT
59 TRIP
OUT
59-2 Overvoltage V>> picked up
OUT
59-2 Overvoltage V>> TRIP
Default Setting
1.20
27-1 Dropout Ratio
1.20
27-2 Dropout Ratio
ON
Current Supervision
Comments