Siemens siprotec SJ62 User Manual page 652

Multi-functional protective relay with local control
Table of Contents

Advertisement

Addr.
Parameter
3122
67Ns-1 DIRECT.
3123
RELEASE DIRECT.
3123
RELEASE DIRECT.
3124
PHI CORRECTION
3125
MEAS. METHOD
3126
RESET DELAY
3127
51Ns I T min
3127
51Ns I T min
3128
51Ns I T knee
3128
51Ns I T knee
3129
51Ns T knee
3130
PU CRITERIA
3131
M.of PU TD
3132
51Ns TD
3140
51Ns Tmin
3140
51Ns T min
3141
51Ns Tmax
3141
51Ns T max
3142
51Ns TIME DIAL
3143
51Ns Startpoint
3301
INTERM.EF
3302
Iie>
3302
Iie>
3302
Iie>
3303
T-det.ext.
3304
T-sum det.
3305
T-reset
3306
Nos.det.
4001
FCT 46
4002
46-1 PICKUP
4003
46-1 DELAY
4004
46-2 PICKUP
4005
46-2 DELAY
4006
46 IEC CURVE
4007
46 ANSI CURVE
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Function
C
Sens. Gnd Fault
Forward
Reverse
Non-Directional
Sens. Gnd Fault
0.001 .. 1.200 A
Sens. Gnd Fault
1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
-45.0 .. 45.0 °
Sens. Gnd Fault
COS ϕ
Sens. Gnd Fault
SIN ϕ
Sens. Gnd Fault
0 .. 60 sec
Sens. Gnd Fault
0.003 .. 1.400 A
Sens. Gnd Fault
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
Sens. Gnd Fault
0.003 .. 0.650 A
Sens. Gnd Fault
1A
0.05 .. 17.00 A
5A
0.25 .. 85.00 A
Sens. Gnd Fault
0.20 .. 100.00 sec
Sens. Gnd Fault
Vgnd OR INs
Vgnd AND INs
1.00 .. 20.00 MofPU; ∞
Sens. Gnd Fault
0.01 .. 999.00 TD
Sens. Gnd Fault
0.05 .. 1.50
Sens. Gnd Fault
0.00 .. 30.00 sec
Sens. Gnd Fault
0.10 .. 30.00 sec
Sens. Gnd Fault
0.00 .. 30.00 sec
Sens. Gnd Fault
0.50 .. 200.00 sec
0.05 .. 15.00 sec; ∞
Sens. Gnd Fault
Sens. Gnd Fault
1.0 .. 4.0
Intermit. EF
OFF
ON
Intermit. EF
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
Intermit. EF
1A
0.05 .. 35.00 A
5A
0.25 .. 175.00 A
Intermit. EF
0.005 .. 1.500 A
Intermit. EF
0.00 .. 10.00 sec
Intermit. EF
0.00 .. 100.00 sec
Intermit. EF
1 .. 600 sec
Intermit. EF
2 .. 10
46 Negative Seq
OFF
ON
46 Negative Seq
1A
0.10 .. 3.00 A
5A
0.50 .. 15.00 A
0.00 .. 60.00 sec; ∞
46 Negative Seq
46 Negative Seq
1A
0.10 .. 3.00 A
5A
0.50 .. 15.00 A
0.00 .. 60.00 sec; ∞
46 Negative Seq
46 Negative Seq
Normal Inverse
Very Inverse
Extremely Inv.
46 Negative Seq
Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
Setting Options
Default Setting
Forward
0.010 A
0.50 A
2.50 A
0.0 °
COS ϕ
1 sec
1.333 A
15.00 A
75.00 A
0.040 A
5.00 A
25.00 A
23.60 sec
Vgnd OR INs
0.20
1.20 sec
0.80 sec
5.80 sec
93.00 sec
1.35 sec
1.1
OFF
1.00 A
5.00 A
1.00 A
5.00 A
1.000 A
0.10 sec
20.00 sec
300 sec
3
OFF
0.10 A
0.50 A
1.50 sec
0.50 A
2.50 A
1.50 sec
Extremely Inv.
Extremely Inv.
A.8 Settings
Comments
67Ns-1 Direction
Release directional element
Release directional element
Correction Angle for Dir. Deter-
mination
Measurement method for Direc-
tion
Reset Delay
51Ns Current at const. Time
Delay T min
51Ns Current at const. Time
Delay T min
51Ns Current at Knee Point
51Ns Current at Knee Point
51Ns Time Delay at Knee Point
Sensitive Ground Fault PICKUP
criteria
Multiples of PU
Time-Dial
51Ns Time Dial
51Ns Minimum Time Delay
51Ns Minimum Time Delay
51Ns Maximum Time Delay
51Ns Maximum Time Delay (at
51Ns PU)
51Ns Time Dial
51Ns Start Point of Inverse
Charac.
Intermittent earth fault protection
Pick-up value of interm. E/F
stage
Pick-up value of interm. E/F
stage
Pick-up value of interm. E/F
stage
Detection extension time
Sum of detection times
Reset time
No. of det. for start of int. E/F prot
46 Negative Sequence Protec-
tion
46-1 Pickup
46-1 Time Delay
46-2 Pickup
46-2 Time Delay
IEC Curve
ANSI Curve
650

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec sj63Siprotec sj64

Table of Contents