Siemens siprotec SJ62 User Manual page 666

Multi-functional protective relay with local control
Table of Contents

Advertisement

Addr.
Parameter
0
PICKUP WITH
0
CURRENT
0
VOLTAGE
0
POWER
0
VOLTAGE SYSTEM
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
T TRIP DELAY
0A
T PICKUP DELAY
0A
T DROPOUT DELAY
0A
BLK.by Vol.Loss
0A
DROPOUT RATIO
0A
DROPOUT RATIO
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Function
C
Flx
Exceeding
Dropping below
Flx
Ia
Ib
Ic
In
In sensitive
Flx
Please select
Va-n
Vb-n
Vc-n
Va-b
Vb-c
Vc-a
Vn
Flx
Ia Va-n
Ib Vb-n
Ic Vc-n
Flx
Phase-Phase
Phase-Earth
Flx
0.05 .. 35.00 A
Flx
0.001 .. 1.500 A
Flx
2.0 .. 260.0 V
Flx
2.0 .. 200.0 V
Flx
45.50 .. 54.50 Hz
Flx
55.50 .. 64.50 Hz
Flx
0.10 .. 20.00 Hz/s
Flx
0.5 .. 10.000 W
Flx
-0.99 .. 0.99
Flx
0.00 .. 3600.00 sec
Flx
0.00 .. 60.00 sec
Flx
0.00 .. 60.00 sec
Flx
NO
YES
Flx
0.70 .. 0.99
Flx
1.01 .. 3.00
Setting Options
Default Setting
Exceeding
Ia
Please select
Ia Va-n
Phase-Phase
2.00 A
0.100 A
110.0 V
110.0 V
51.00 Hz
61.00 Hz
5.00 Hz/s
200.0 W
0.50
1.00 sec
0.00 sec
0.00 sec
YES
0.95
1.05
A.8 Settings
Comments
Pickup with
Current
Voltage
Power
Voltage System
Pickup Threshold
Pickup Threshold
Pickup Threshold
Pickup Threshold
Pickup Threshold
Pickup Threshold
Pickup Threshold
Pickup Threshold
Pickup Threshold
Trip Time Delay
Pickup Time Delay
Dropout Time Delay
Block in case of Meas.-Voltage
Loss
Dropout Ratio
Dropout Ratio