Siemens siprotec SJ62 User Manual page 658

Multi-functional protective relay with local control
Table of Contents

Advertisement

Addr.
Parameter
6420
T-CB close
6421
Balancing V1/V2
6422A
ANGLE ADJUSTM.
6423
CONNECTIONof V2
6425
VT Vn2, primary
6430
dV ASYN V2>V1
6431
dV ASYN V2<V1
6432
df ASYN f2>f1
6433
df ASYN f2<f1
6440
SYNC PERMIS.
6441
F SYNCHRON
6442
dV SYNC V2>V1
6443
dV SYNC V2<V1
dα SYNC α2> α1
6444
dα SYNC α2< α1
6445
6446
T SYNC-DELAY
6450
dV SYNCHK V2>V1
6451
dV SYNCHK V2<V1
6452
df SYNCHK f2>f1
6453
df SYNCHK f2<f1
dα SYNCHK α2>α1
6454
dα SYNCHK α2<α1
6455
7001
FCT 50BF
7004
Chk BRK CONTACT
7005
TRIP-Timer
7101
FCT 79
7103
BLOCK MC Dur.
7105
TIME RESTRAINT
7108
SAFETY 79 ready
7113
CHECK CB?
7114
T-Start MONITOR
7115
CB TIME OUT
7116
Max. DEAD EXT.
7117
T-ACTION
7118
T DEAD DELAY
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Function
C
SYNC function 4
0.01 .. 0.60 sec
SYNC function 4
0.50 .. 2.00
0 .. 360 °
SYNC function 4
SYNC function 4
A-G
B-G
C-G
A-B
B-C
C-A
SYNC function 4
0.10 .. 800.00 kV
SYNC function 4
0.5 .. 50.0 V
SYNC function 4
0.5 .. 50.0 V
SYNC function 4
0.01 .. 2.00 Hz
SYNC function 4
0.01 .. 2.00 Hz
SYNC function 4
YES
NO
SYNC function 4
0.01 .. 0.04 Hz
SYNC function 4
0.5 .. 50.0 V
SYNC function 4
0.5 .. 50.0 V
2 .. 80 °
SYNC function 4
2 .. 80 °
SYNC function 4
SYNC function 4
0.00 .. 60.00 sec
SYNC function 4
0.5 .. 50.0 V
SYNC function 4
0.5 .. 50.0 V
SYNC function 4
0.01 .. 2.00 Hz
SYNC function 4
0.01 .. 2.00 Hz
2 .. 80 °
SYNC function 4
2 .. 80 °
SYNC function 4
50BF BkrFailure
OFF
ON
50BF BkrFailure
OFF
ON
0.06 .. 60.00 sec; ∞
50BF BkrFailure
79M Auto Recl.
OFF
ON
79M Auto Recl.
0.50 .. 320.00 sec; 0
79M Auto Recl.
0.50 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
No check
Chk each cycle
0.01 .. 320.00 sec; ∞
79M Auto Recl.
79M Auto Recl.
0.10 .. 320.00 sec
0.50 .. 1800.00 sec; ∞
79M Auto Recl.
0.01 .. 320.00 sec; ∞
79M Auto Recl.
0.0 .. 1800.0 sec; ∞
79M Auto Recl.
Setting Options
Default Setting
0.06 sec
1.00
0 °
A-B
12.00 kV
2.0 V
2.0 V
0.10 Hz
0.10 Hz
YES
0.01 Hz
5.0 V
5.0 V
10 °
10 °
0.00 sec
5.0 V
5.0 V
0.10 Hz
0.10 Hz
10 °
10 °
OFF
OFF
0.25 sec
OFF
1.00 sec
3.00 sec
0.50 sec
No check
0.50 sec
3.00 sec
100.00 sec
∞ sec
1.0 sec
A.8 Settings
Comments
Closing (operating) time of CB
Balancing factor V1/V2
Angle adjustment (transformer)
Connection of V2
VT nominal voltage V2, primary
Maximum voltage difference
V2>V1
Maximum voltage difference
V2<V1
Maximum frequency difference
f2>f1
Maximum frequency difference
f2<f1
Switching at synchronous condi-
tions
Frequency threshold ASYN <-->
SYN
Maximum voltage difference
V2>V1
Maximum voltage difference
V2<V1
Maximum angle difference
alpha2>alpha1
Maximum angle difference
alpha2<alpha1
Release delay at synchronous
conditions
Maximum voltage difference
V2>V1
Maximum voltage difference
V2<V1
Maximum frequency difference
f2>f1
Maximum frequency difference
f2<f1
Maximum angle difference
alpha2>alpha1
Maximum angle difference
alpha2<alpha1
50BF Breaker Failure Protection
Check Breaker contacts
TRIP-Timer
79 Auto-Reclose Function
AR blocking duration after
manual close
79 Auto Reclosing reset time
Safety Time until 79 is ready
Check circuit breaker before AR?
AR start-signal monitoring time
Circuit Breaker (CB) Supervision
Time
Maximum dead time extension
Action time
Maximum Time Delay of Dead-
Time Start
656