Siemens siprotec SJ62 User Manual page 655

Multi-functional protective relay with local control
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
6123
CONNECTIONof V2
6125
VT Vn2, primary
6130
dV ASYN V2>V1
6131
dV ASYN V2<V1
6132
df ASYN f2>f1
6133
df ASYN f2<f1
6140
SYNC PERMIS.
6141
F SYNCHRON
6142
dV SYNC V2>V1
6143
dV SYNC V2<V1
dα SYNC α2> α1
6144
dα SYNC α2< α1
6145
6146
T SYNC-DELAY
6150
dV SYNCHK V2>V1
6151
dV SYNCHK V2<V1
6152
df SYNCHK f2>f1
6153
df SYNCHK f2<f1
dα SYNCHK α2>α1
6154
dα SYNCHK α2<α1
6155
6201
Synchronizing
6202
SyncCB
6203
Vmin
6204
Vmax
6205
V<
6206
V>
6207
SYNC V1<V2>
6208
SYNC V1>V2<
6209
SYNC V1<V2<
6210A
Direct CO
6211A
TSUP VOLTAGE
6212
T-SYN. DURATION
6213A
25 Synchron
6220
T-CB close
6221
Balancing V1/V2
653
Function
C
SYNC function 1
A-G
B-G
C-G
A-B
B-C
C-A
SYNC function 1
0.10 .. 800.00 kV
SYNC function 1
0.5 .. 50.0 V
SYNC function 1
0.5 .. 50.0 V
SYNC function 1
0.01 .. 2.00 Hz
SYNC function 1
0.01 .. 2.00 Hz
SYNC function 1
YES
NO
SYNC function 1
0.01 .. 0.04 Hz
SYNC function 1
0.5 .. 50.0 V
SYNC function 1
0.5 .. 50.0 V
2 .. 80 °
SYNC function 1
2 .. 80 °
SYNC function 1
SYNC function 1
0.00 .. 60.00 sec
SYNC function 1
0.5 .. 50.0 V
SYNC function 1
0.5 .. 50.0 V
SYNC function 1
0.01 .. 2.00 Hz
SYNC function 1
0.01 .. 2.00 Hz
2 .. 80 °
SYNC function 1
2 .. 80 °
SYNC function 1
SYNC function 2
ON
OFF
SYNC function 2
(Setting options depend
on configuration)
SYNC function 2
20 .. 125 V
SYNC function 2
20 .. 140 V
SYNC function 2
1 .. 60 V
SYNC function 2
20 .. 140 V
SYNC function 2
YES
NO
SYNC function 2
YES
NO
SYNC function 2
YES
NO
SYNC function 2
YES
NO
SYNC function 2
0.00 .. 60.00 sec
0.01 .. 1200.00 sec; ∞
SYNC function 2
SYNC function 2
YES
NO
SYNC function 2
0.01 .. 0.60 sec
SYNC function 2
0.50 .. 2.00
Setting Options
Default Setting
A-B
12.00 kV
2.0 V
2.0 V
0.10 Hz
0.10 Hz
YES
0.01 Hz
5.0 V
5.0 V
10 °
10 °
0.00 sec
5.0 V
5.0 V
0.10 Hz
0.10 Hz
10 °
10 °
OFF
None
90 V
110 V
5 V
80 V
NO
NO
NO
NO
0.10 sec
30.00 sec
YES
0.06 sec
1.00
Comments
Connection of V2
VT nominal voltage V2, primary
Maximum voltage difference
V2>V1
Maximum voltage difference
V2<V1
Maximum frequency difference
f2>f1
Maximum frequency difference
f2<f1
Switching at synchronous condi-
tions
Frequency threshold ASYN <-->
SYN
Maximum voltage difference
V2>V1
Maximum voltage difference
V2<V1
Maximum angle difference
alpha2>alpha1
Maximum angle difference
alpha2<alpha1
Release delay at synchronous
conditions
Maximum voltage difference
V2>V1
Maximum voltage difference
V2<V1
Maximum frequency difference
f2>f1
Maximum frequency difference
f2<f1
Maximum angle difference
alpha2>alpha1
Maximum angle difference
alpha2<alpha1
Synchronizing Function
Synchronizable circuit breaker
Minimum voltage limit: Vmin
Maximum voltage limit: Vmax
Threshold V1, V2 without voltage
Threshold V1, V2 with voltage
ON-Command at V1< and V2>
ON-Command at V1> and V2<
ON-Command at V1< and V2<
Direct ON-Command
Supervision time of V1>;V2> or
V1<;V2<
Maximum duration of Synchroni-
zation
Switching at synchronous condi-
tion
Closing (operating) time of CB
Balancing factor V1/V2
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015